期刊文献+

开式通风系统作用下深埋地铁区间隧道火灾的性能化分析 被引量:3

Analysis on the Performance of Interzone Tunnel Fire in Deeply-Buried Subway under the Effect of the Open Ventilation System
下载PDF
导出
摘要 目的分析中部风井对深埋地铁区间隧道火灾烟气蔓延的影响,以及中部逃生井正压送风作用下逃生井的安全疏散性状,为深埋地铁工程的性能化防火设计提供理论支持.方法采用火灾动力学软件(FDS)进行数值模拟,采集烟气温度、浓度等参数,分析开式通风系统作用下火灾烟气蔓延的规律.结果当在深埋地铁区间隧道中部附近设置排烟风井时,烟囱效应作用加强了烟气通过风井的自由出流,降低了隧道内烟气浓度及温度,可以为人员疏散争取一定的时间.结论深埋地铁区间隧道中部逃生井采用正压送风措施,很好地抑制了隧道火灾烟气的蔓延态势,可以充分满足人员安全疏散的要求. The project is to study the effect of intermediate shaft on the spread of fire smoke in the interzone tunnel in deeply-buried subways, safe evacuation performance with intermediate escape shaft associated with positive pressure air supply, and to provide valuable theoretical support for the subway engineering project design based on the performance of fire safety. Fire dynamics simulator (FDS)is applied to simulate mass concentration of fire smoke and smoke temperature, and smoke spread law is analyzed under the open venti- lation system in a tunnel of deeply-buried subway. The results indicate that the tunnel smoke concentration and temperature are reduced when the smoke exhaust shaft are established near the centre of interzone tun- nel, which can get more time for safety evacuation. Furthermore, when positive pressure air is supplied in the intermediate shaft, it can fully satisfy safe evacuation conditions for evacuees. The research result also indi- cate when positive pressure air is supplied in the intermediate escape shaft, it can fully control the spread of fire smoke in the tunnel and satisfy safe evacuation conditions for evacuees.
出处 《沈阳建筑大学学报(自然科学版)》 CAS 北大核心 2011年第5期925-930,共6页 Journal of Shenyang Jianzhu University:Natural Science
基金 国家自然科学基金项目(91024022) 辽宁省自然科学基金项目(20100266) 住房和城乡建设部研究开发项目(2007-K3-5)
关键词 深埋地铁 区间隧道 火灾 中间竖井 正压送风 deeply-buried subway regional tunnel fire intermediate shaft positive pressure air supply
  • 相关文献

参考文献16

二级参考文献17

  • 1王国栋,霍然,易亮,周允基.热烟测试用于评价建筑烟控系统的讨论[J].消防科学与技术,2005,24(1):25-27. 被引量:16
  • 2李为为,唐祯敏.地铁运营事故分析及其对策研究[J].中国安全科学学报,2004,14(6):105-108. 被引量:78
  • 3刘国芳.北京地铁通风系统的现状分析和改进意见[J].铁道建筑,1995,35(3):15-18. 被引量:17
  • 4[6]Safety systems in underground tunnels of the Bilbao metro.Tunneling and Underground Space Technology , 2004, 19(4-5):309
  • 5[8]Mashimo, H.. State of the road tunnel safety technology in Japan. Tunneling and Underground Space Technology,2002,17 ( 2 ): 145-152
  • 6[9]Yamada, N.; Ota, Y.. Safety Systems for the Trans-Tokyo Bay Highway Tunnel Project. Tunneling and Underground Space Technology, 1999, 14 ( 1 ) : 3-12
  • 7[10]Beroggi, Giampiero E.G.. Integrated safety planning for underground systems. Journal of Hazardous Materials ,2000,71 ( 1-3 ): 17-34
  • 8[10]Zhong Maohua,Fan Weicheng,Liu Tiemin.Safety evaluation of engineering and construction projects in China,Journal of Luss Prevention in the Process Industries,2003,16(3):201 ~ 207
  • 9冯炼.地铁网络系统环境控制数值模拟研究.西南交通大学博士学位论文[M].,2001,6..
  • 10GB50157-2003.地铁设计规范[S].[S].,..

共引文献232

同被引文献34

引证文献3

二级引证文献38

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部