半波长输电线路故障暂态过电压特性研究 被引量:16

Research on Characteristics of Transient Overvoltages Caused by Faults Occurred in Half-Wave Length AC Transmission Lines
下载PDF
导出
摘要 阐述了半波长输电线路故障暂态过程的沿线电压分布特性,构建了典型特高压半波长输电线路的仿真模型,采用电磁暂态计算程序对线路单相接地故障、自动重合闸过程的过电压进行了分析,研究了线路传输功率、人工调谐网络、线路长度等因素对线路故障暂态过电压的影响。分析了沿线装设多组避雷器对半波长输电线路故障暂态过电压的抑制效果,研究了避雷器的安装位置与安装数量对故障暂态过电压水平的影响。仿真结果表明,沿线装设5组避雷器时,半波长输电线路故障暂态过电压水平可限制在1.60 pu以下,但对避雷器的通流容量要求较高。研究结果为发展半波长交流输电技术提供了参考依据。 The distribution behavior of the temporary overvoltages caused by single-phase-to-ground fault along half-wavelength AC transmission line (HWACTL) is expounded and a simulation model for typical HWACTL is built. The overvotlages caused by single-phase-to-ground fault and autoreclsore process are analyzed by ATP-EMTP software, and the impacts of such factors as transmission capacity, artificial tuning and line length on transient overvoltage of tranmission line are researched. The effect of suppressing fault-caused transient overvotlage in HWACTL by installing multi-set of metal oxide an'ester (MOA) along HWACTL is analyzed and the influences of both installation positions and installation number of MOAs on fanlt-caused transient overvoltage level are researched. Simulation results show that when five sets of MOA are inistalled along the line, the fault-caused overvoltage of HWACTL can be restricted to lower than 1.6 pu, however the discharge capacity of MOA should be higher.
出处 《电网技术》 EI CSCD 北大核心 2012年第2期43-47,共5页 Power System Technology
基金 国家电网公司科技项目(B11-10-023)~~
关键词 半波长 单相接地故障 故障暂态过电压 人工调谐网络 金属氧化物避雷器 half-wavelength single phase-to-ground fault fault-caused transient overvoltages artificial tuning network metal oxide arrester(MOA)
  • 相关文献

参考文献15

二级参考文献107

共引文献207

同被引文献114

引证文献16

二级引证文献87

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部