期刊文献+

锅炉水碱度测量的PLSR方法研究 被引量:3

PLSR Method in Boiler Water Basicity Measurement
下载PDF
导出
摘要 通过偏最小二乘回归方法对由FIA分析系统得到的FIA峰和混合碱中NaOH和Na_2CO_3浓度的对数之间进行拟合,间接得到锅炉水中NaOH和Na_2CO_3的含量。实验和数据处理结果表明,在NaOH和Na_2CO_3,浓度都为2~100mg/L的锅炉水样中,使用KS-PLSR检测出的两者的平均相对误差分别为1.10%和2.01%,说明KS-PLSR方法对锅炉水碱度检测的有效性。 Through PLSR method,having the FIA peak area and the logarithms of Na2 CO3 and NaOH mixed bases fitted so as to measure Na2CO3 and NaOH contents in boiler water indirectly.Both experimental and analytical results show that when measuring the boiler water sample which boasting of 2 to 100mg/L Na2CO3 and NaOH respectively,the average relative errors with the KS-PLSR method are 1.10%and 2.01%respectively, this proves the effectiveness of KS-PLSR method in measuring boiler water basicity.
出处 《化工自动化及仪表》 CAS 北大核心 2011年第12期1445-1448,共4页 Control and Instruments in Chemical Industry
基金 江苏省科技支撑项目(BF2010748)
关键词 偏最小二乘回归 流动注射分析 预测误差 Kennard-Stone分类 partial least square regression(PLSR) flow injection analysis(FIA) prediction error KennardStone classification