500kV隔离开关控制接触器频繁故障的原因分析及反事故措施 被引量:4

Cause Analysis of Frequent Breakdown and Anti-accident Measures for Control Contactor in 500 kV Disconnecter
原文传递
导出
摘要 通过分析500kV隔离开关控制接触器在操作过程中的电压、电流波形,认为在接触器线圈励磁返回瞬间,线圈回路出现的暂态冲击是造成其频繁故障的原因,提出了在接触器线圈两端加装消弧回路的反事故措施。通过对2种消弧回路的效果对比,最终选择加装二极管串联电阻的消弧回路。 Frequent breakdown occurs for control contactor in 500 kV disconnecter,due to the transient arc surge appearing in the coil circuit at the moment of excitation return,by analyzing the voltage and current waveforms during the operation of control contactor.Therefore,the anti-accident measures are proposed by applying the arc suppression circuit to the control contactor coil.By comparing the effect of two kinds of arc suppression circuit,an arc suppression circuit with the diode and series resistance is selected.
出处 《电力建设》 2012年第2期88-91,共4页 Electric Power Construction
关键词 隔离开关 控制接触器 暂态冲击 消弧回路 disconnector control contactor transient arc surge arc suppression circuit