期刊文献+

给水泵切换引发锅炉汽包缺水事故的研究

Research on Water Shortage Fault Caused by Feed Pump Switching in Boiler Steam Drum
下载PDF
导出
摘要 通过分析给水泵切换引发的锅炉汽包缺水事故,查明了发生故障的首要原因为操作失误,其次为给水泵出口逆止阀和电动闸阀均有故障,提出了切换给水泵的正确操作步骤和注意事项,并给出了电动闸阀执行器选型和给水泵入口管道设计的具体建议。 Based on the analysis of the water shortage caused by feed pump switching in boiler steam drum, the main reason of the fault is ascertained to be mal-operation, while the non-return valve and electric gate valve also present fault. In this paper, it points out correct operation steps and attentions that should be paid to switch feed pump, and suggestions are given for the choosing of electric gate valve controlling element and the design of feed pump entrance pipe.
出处 《山西电力》 2012年第1期51-53,共3页 Shanxi Electric Power
关键词 汽包缺水 给水泵 逆止阀 电动闸阀 water shortage of boiler steam drum switch of feed pump non-return valve electric gate valve
  • 相关文献

参考文献2

  • 1河南省电力公司.火电工程调试技术手册汽轮机卷[M].北京:中国电力出版社,2002:87—88.
  • 2山西省电力工业局.汽轮机设备运行[M].北京:中国电力出版社,1997.

共引文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部