基于SCADA系统OPC通信的供水管网实时模拟 被引量:2

The real time simulation of urban water distribution network based on OPC communication of SCADA
下载PDF
导出
摘要 建立基于SCADA系统OPC通信的城市供水管网实时模拟系统,结合管网实时运行信息与管网数字化分析系统,实现供水管网实时动态模拟分析;利用数据采集与监控(SCADA)软件对OPC的支持,实时获得供水管网运行信息,以供水管网数字化分析系统为基础,通过实时监测流量和压力数据驱动模型,对供水管网运行工况进行实时仿真模拟;实现了供水管网实时模拟、压力在线监测信息实时显示与数据报警功能,能够及时发现管网运行异常工况;供水管网实时模拟系统解决了传统供水管网数字化分析系统数据访问、有人参与等问题,为智能供水管网的发展提供了新思路. To combine the real-time run-off information and digital analysis system of water distribution network,and realize the real-time simulation and dynamic analysis for water distribution network,an urban water distribution network real time simulation system based on OPC communication of SCADA system was built up in this paper.Using SCADA software for OPC communication,the real-time operation information for water distribution network was gained.The simulation model was driven by real time monitoring flow and pressure data to simulate water distribution,to display pressure results online and to alarm pressure.The abnormal operation scenario could be detected in real time.The simulation system solved the problem of data input and user interaction of traditional network model,and offered a new idea for the development of intelligence water network.
出处 《哈尔滨工业大学学报》 EI CAS CSCD 北大核心 2011年第12期63-67,共5页 Journal of Harbin Institute of Technology
基金 国家科技支撑计划资助项目(2006BA08B03)
关键词 城市供水管网 数字化平台 实时模拟 数字采信与监控系统 智能管网 Urban water distribution network digital platform real-time simulation supervisory control and data acquisition(SCADA) system intelligence water network
  • 相关文献

参考文献13

  • 1WATSON J P, MURRAY R, HART W. Formulation and optimization of robust sensor placement problems for drinking water contamination warning systems [ J ]. Journal of Infrastructure Systems, 2009, 15 (4) :330 - 339.
  • 2ALFONSO L, JONOSKI A, SOLOMATINE D. Muhiobjective optimization of operational responses for contaminant flushing in water distribution networks [ J ]. Journal of Water Resources Planning and Management, 2010, 136(1) :48 -58.
  • 3RECA J, MARTINEZ J, BANOS R, et al. Optimal design of gravity - fed looped water distribution networks considering the resilience index [ J ].Journal of Water Resources Planning and Management, 2008, 134 ( 3 ) : 234 - 238.
  • 4IZQUIERDOA J, MONTALVOB I, PEREZA R, et al.Sensitivity analysis to assess the relative importance of pipes in water distribution networks [ J ].Mathematical and Computer Modelling, 2008, 48:268 -278.
  • 5KLEINER Y, ADAMS B J, ROGERS J S. Water distribution network renewal planning [ J ]. Journal of Computing in Civil Engineering, 2001, 15 ( 1 ) : 15 - 26.
  • 6WEBER C, BUNN S. Water distribution optimization: taking scada one step forward [ C ]//Proceedings of World Environmental and Water Resources Congress. Kansas : [ s. n. ] ,2009 : 2182 - 2190.
  • 7路小俊,冬大龙,宋斌,唐成虹.基于OPC技术的风电厂数据采集与监控系统方案[J].电力系统自动化,2008,32(23):90-94. 被引量:42
  • 8郭圣安.城市供水调度SCADA系统的应用与发展[J].工业控制计算机,2009,22(4):29-30. 被引量:5
  • 9OPC Foundation. OPC data access custom interface specification version 3.0 [ EB/OL ]. http://www. orgfoundation, org, 2003.
  • 10ROSSMAN L A. The EPANET programmer' s tookit for analysis of water distribution systems [ C ]//Proceedings of the Annual Water Resources Planning and Management Conference. Reston: CD - ROM, ASCE, 1999:61 - 76.

二级参考文献13