摘要 对输电铁塔主材断裂进行了失效分析,通过承载力计算,化学成分、常温和低温力学性能试验以及对失效塔材断口、金相组织分析,探讨并明确失效原因,提出防范措施。结果表明:塔材为低温脆断,而冲孔形成的微裂纹是导致塔材低温失效的主要原因。 Fracture of primary materials in transmission tower is analyzed, main conclusions of material failure are drawn and suggestions for improvement is put forward by analyzing bearing capacity, chemical properties, low-temperature tensile properties, fracture part of main material and microstructure of the main fracture material. The results show that main reason for material failure is low-temperature brittle fracture which is mainly caused by cracks in the process of punching.
出处 《电力建设》 2012年第3期86-88,共3页 Electric Power Construction
关键词 输电铁塔 低温 脆性断裂 角钢 transmission tower low-temperature brittle fracture angle steel
  • 相关文献

参考文献9

二级参考文献13

共引文献59

同被引文献44

  • 1张伍康.转角塔基础预偏的分析与处理[J].福建电力与电工,2003,23(1):7-8. 被引量:3
  • 2孟庆国,方洪渊,徐文立,姬书得.考虑金属逐步填充的多道焊温度场数值模拟[J].焊接学报,2004,25(5):53-55. 被引量:12
  • 3王元清,武延民,石永久,王晓哲,张玉玲.低温对结构钢材主要力学性能影响的试验研究[J].铁道科学与工程学报,2005,2(1):1-4. 被引量:45
  • 4GB/T3077-1999.合金结构钢[S].[S].,..
  • 5VISHNEVSKY C, STCIGERWALD E A. Influence of alloying elements on the toughness of low alloy mar- tensitic high strength steels [R// Report CR 68-09 (F). Watertowm Army Materials and Mechanics Re search Center, 1968.
  • 6DAHL W, KRETZCHMANN W B. Influence of pre- cracking and grain size on fracture toughness of struc- ture steelsFJ. Fracture, 1977,2A. 17-21.
  • 7GB/T10561-2005钢中非金属夹杂物含量的测定-标准评级图显微检验法.
  • 8DL/T 5154-2012架空输电线路杆塔结构设计技术规定[S].
  • 9GB50790-2013,±800kV直流架空输电线路设计规范[S].
  • 102003GB.钢结构设计规范[S].