摘要 引用三圈变压器等效负载损耗的概念,推导出了两台同容量三圈变压器并列运行的经济负荷功率、经济负荷率、经济运行效率和两台同容量三圈变压器并列经济运行投切台数临界功率的计算公式。以某降压变电所的两台同容量SFSL1- 31500/110型三相三绕组电力变压器为实际算例说明了上述公式的实际用法。 Appointing the concept of equivalent load loss of the three-winding transformer,derived out the calculation formulas of two same capacity three-winding transformer economical operation load rate,economic operation efficiency and the threshold power of sets number put into and get off of the parallel operation three-winding transformer with the same capacity..It explains the practice usage of the formula above-mentioned with two type SFSL1-31500/110 three-winding transformer of 110kV step down substation as a practice calculation example.
出处 《大众科技》 2012年第3期119-121,共3页 Popular Science & Technology
关键词 三圈变压器 等效负载损耗 经济负荷率 经济运行效率 投切台数临界功率 three-winding transformer equivalent load loss economic load rate efficiency of economic operation the threshold power of sets number put into and get off
  • 相关文献

参考文献3

二级参考文献4

  • 1胡景生.变压器效能与节电技术[M].北京:机械工业出版社,2007.100-138.
  • 2方大干.变压器速查速算手册[M].北京:中国水利水电出版社,2004.
  • 3全德生,金盛.供电企业电能损耗与无功管理手册[M].北京:中国电力出版社,2005.
  • 4王亚忠.双绕组变压器经济运行负载系数研究[J].电力系统保护与控制,2008,36(17):60-61. 被引量:26

共引文献26