期刊文献+

两种典型地板送风系统形式热舒适模拟分析

Numerical Study on Thermal Comfort of Two Typical Forms of Underfloor Air Distribution System
下载PDF
导出
摘要 通过模拟地板送风系统的两种典型系统形式,从获得的温度场、速度场、PMV场表明,下送上回系统较容易满足垂直空气温差的限值,下送下回系统容易超出垂直空气温差的限值,在低热力长度尺度(lm/H)时下送下回系统比下送上回系统容易获得舒适的环境,在高热力长度尺(lm/H)时,两种系统形式均易产生偏冷的室内环境。 Through the simulation of two typical forms of underfloor air distribution system,the velocity field and temperature field,PMV field were obtained,the results show that the Top Return system(TR) is easy to satisfy the vertical air temperature difference limits,while the Floor Return system(FR) is easy to exceed the vertical air temperature difference limits,and FR will easily obtain comfortable indoor climate when the thermal length scale(lm/H) is low,both of FR and TR will lightly generate a cold indoor environment when the thermal length scale(lm/H) is high.
出处 《建筑热能通风空调》 2012年第1期61-64,共4页 Building Energy & Environment
关键词 地板送风系统 热舒适 数值模拟 热力长度尺度 Under Floor Air Distribution system(UFAD) thermal comfort numerical simulation thermal length scale
  • 相关文献

参考文献12

  • 1Bauman F,Webster T.Outlook for underfloor air distribution[J].ASHRAE Journal,2001,43(6):18-27.
  • 2孔琼香,俞炳丰.办公楼地板送风系统应用与研究现状[J].暖通空调,2004,34(4):26-31. 被引量:25
  • 3杨国荣,方伟.地板送风设计指南[M].北京:中国建筑工业出版社,2006.
  • 4林忠平 范存养 徐文华.办公楼地板送风技术的新进展.暖通空调,2005,35(10):18-35.
  • 5De Carli,M Peron,F Romagnoni,et al.Analysis of air velocityand temperature distribution in furnished rooms with underfloorair diffusers[A].In:Proceedings of ROOMVENT 2000[C].2000,(1):687-692.
  • 6Wan M P,Chao C Y.Experimental study of thermal comfort inan office environment with an underfloor ventilation system[J].Indoor Built Environment,2002,(11):250-265.
  • 7Wan M P,Chao C Y.Numerical and experimental study ofvelocity and temperature characteristics in a ventilated enclosurewith an underfloor ventilation systems[J].Indoor Air,2005,15:342-355.
  • 8Chen Qingyan,Xu Weiran.A zero-equation turbulence model forindoor airflow simulation[J].Energy and Building,1998,28:131-144.
  • 9Chen Q,Moser A.Simulation of a multiple-nozzle diffuser[A].In:Proceedings of the 12th AIVC Conference on Air Movementand Ventilation Control within Buildings[C].Ottawa,1991,(2):1-13.
  • 10吴玉涛,李强民,邓时凯.办公建筑中旋流风口地板送风系统的设计及实验研究[J].暖通空调,2006,36(2):71-75. 被引量:6

二级参考文献53

  • 1马仁民.地板送风技术条件与舒适条件的研究[J].暖通空调,1995,25(6):45-46. 被引量:30
  • 2龙惟定.上海的建筑节能与空调冷热源[J].暖通空调,1996,26(4):23-28. 被引量:35
  • 3Chen Qingyan,Glicksman L R.System Performance Evaluation and Design Guidelines for Displacement Ventilation[M].Atlanta:ASHRAE,2003.
  • 4Bauman F S.Underfloor Air Distribution(UFAD)Design Guide[M].Atlanta:ASHRAE,2003.
  • 5ASHRAE.ASHRAE Standard 62-1989 Ventilation for acceptable indoor air quality[S].
  • 6ASHRAE.ANSI/ASHRAE Standard 55-1992 Thermal environment conditions for human occupancy[S].
  • 7ASHRAE.ASHRAE Handbook Fundamentals[M].Atlanta:ASHRAE,1997.
  • 8Filler M.Best practices for underfloor air system[J].ASHRAE J,2004,46(10):39-42.
  • 9Chao C Y H,Wan M P.Airflow and air temperature distribution in the occupied region of an underfloor ventilation system[J].Building and Environment,2004,39(10):749-762.
  • 10邓伟鹏 吴岚 李强民.上海某办公大楼置换通风空调系统的设计及应用[C].1-10.2001年全国置换通风应用研讨会论文集[C].,2001..