摘要 介绍了现有数字化变电站的2种组网模式。分析了IEC 61850-9-1的采样值点对点传输方案以及IEC61850-9-2的采样值网络传输方案;提出了一种应用VLAN技术的IEC 61850-9-2采样值网络和GOOSE网络共网传输的方案,从技术,经济角度分析了其可行性;并对过程层的采样值,GOOSE数据报文进行了流量分析。结合某数字化变电站试点工程,采用OPNET仿真软件对共网传输中IED设备的端到端延时进行了仿真分析,结果表明采用VLAN技术的共网传输方案可行。 Two networking modes are presented for digital substations.The SMV point-to-point transmission mode based on IEC 61850-9-1 and the SMV network transmission mode based on IEC 61850-9-2 are both analyzed.A VLAN-based common network transmission scheme is proposed for IEC 61850-9-2 SMV and GOOSE,proved practical technically and economically;the traffic analysis is made about SMV and GOOSE packets in process level.In combination with a pilot digital substation project,simulation analysis about end-to-end delay of IED in common network transmission is conducted by means of OPNET software,which verifies the feasibility of the proposed scheme.
作者 宋园果 舒勤
出处 《华东电力》 北大核心 2012年第3期467-472,共6页 East China Electric Power
基金 四川省科技支撑计划项目(2009GZ0155) 四川省电力公司科技项目(09h0913)~~
关键词 数字化变电站 虚拟局域网 共网传输 digital substation virtual local area network common network transmission