摘要
研究了曝气吹脱法对水中1,1,1-三氯乙烷和1,1,2-三氯乙烷的去除效果。结果表明,曝气吹脱法对水中1,1,1-三氯乙烷具有理想的去除效果,但是对1,1,2-三氯乙烷的去除效果很差;当曝气量为0.4~1.0 L/min,气水比为3~5时,能将初始质量浓度为5倍国家标准限值的1,1,1-三氯乙烷降低至《生活饮用水卫生标准》(GB 5749—2006)限值以内;在相同曝气量条件下,气水比越大,对1,1,1-三氯乙烷的去除效果越好。
The removal effects of 1, 1, 1 - trichloroethane and 1, 1,2 - trichloroethane in water by aeration stripping method were studied. The results showed that aeration stripping method had satisfied removal effect on 1, 1, 1 - trichloroethane, but it had bad removal effect on 1, 1,2 - trichloroethane. The initial concentration of 1, 1, 1 - trichloroethane which was 5 times of state standard limit value could be reduced below the limit value of Standards for Drinking Water Quality( GB 5749--2006 ) when aeration flow was 0.4 to 1.0 L/min and gas-water ratio was 3 to 5. The greater of gas-water ratio was, the better of 1, 1, 1 - trichloroethane removal effect was with the same aeration flow conditions.
出处
《供水技术》
2012年第2期34-36,共3页
Water Technology
基金
国家水体污染控制与治理科技重大专项(2008ZX07420-005)
关键词
曝气吹脱
曝气流量
气水比
三氯乙烷
aeration stripping
aeration now
gas-water ratio
trichloroethane