摘要 A simulation system for power grid with concentrated large-scale wind farm integration is established based on the electro-magnetic transient model of wind turbine equipped with doubly-fed induction generator (DFIG),which is built by real-time digital simulator (RTDS).Using the hardware communication interface of RTDS,a closed-loop testing experiment is accomplished to study the impacts of large-scale wind farms on the existing relay protection devices for wind farm outgoing transmission line.This paper points out problems existing in current relay protection devices as follows:fault phase selector can select unwanted phase due to the changes of fault features caused by special network connection of wind farms;blocking condition for distance protections needs to be re-examined due to the weak power-feed characteristics of wind farms;and power frequency parameter based relay protection devices cannot accurately operate due to the special transient voltage and current characteristics of wind farms during fault period.Results lay the foundation for improving the performances of the existing relay protection device and developing new principle relay protection. A simulation system for power grid with concentrated based on the electro-magnetic transient model of wind turbine (DFIG), which is built by real-time digital simulator (RTDS) large-scale wind farm integration is established equipped with doubly-fed induction generator Using the hardware communication interface of RTDS, a closed-loop testing experiment is accomplished to study the impacts of large-scale wind farms on the existing relay protection devices for wind farm outgoing transmission line. This paper points out problems existing in current relay protection devices as follows: fault phase selector can select unwanted phase due to the changes of fault features caused by special network connection of wind farms; blocking condition for distance protections needs to be re-examined due to the weak power-feed characteristics of wind farms; and power frequency parameter based relay protection devices cannot accurately operate due to the special transient voltage and current characteristics of wind farms during fault period. Results lay the foundation for improving the performances of the existing relay protection device and developing new principle relay protection.
出处 《电力系统自动化》 EI CSCD 北大核心 2012年第8期148-153,共6页 Automation of Electric Power Systems
基金 supported by the Special Fund of the National Basic Research Program of China (973 Program) (No.2009CB219704)
关键词 继电保护装置 大型风电场 保护性能 输电线路 双馈风力发电机 双馈感应发电机 实时数字仿真 线路保护装置 wind farm transmission line relay protection doubly-fed induction generator (DFIG) real-time digitalsimulator (RTDS)
  • 相关文献

参考文献10

二级参考文献121

共引文献1834

同被引文献73

引证文献3

二级引证文献37

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部