摘要
通过分析毛细管内液柱的动量方程,从力平衡的角度获得毛细相变流体回路系统的启动判别条件,并建立蒸发器的三维导热模型来研究系统的启动特性.研究表明:蒸发器的启动预热时间随启动热流的增大而减小;减小液体补偿腔的高度可以加快蒸发器的启动过程,且启动热流愈小该现象愈显著;在较低的启动热流条件下,减小蒸气槽道的宽度,可以减小启动预热时间,改善蒸发器启动性能,而在较高的热流密度下,其对蒸发器的启动性能影响不大.
The start-up criterion of the capillary loop system with phase change was obtained by analyzing the force equilibrium of the capillary liquid column,and a three-dimensional thermal conducting model of the evaporator is established to investigate the start-up characteristics of the system.The results show that the preheating time of the evaporator decreases with increasing of the heat flux;reducing the height of the liquid compensation chamber can speed up the startup process of the evaporator and the effect would be more significant under a lower startup heat flux;besides,the preheating time can be shortened by reducing the width of the steam channels under lower startup heat flux,while the effects are not significant under high heat flux.
出处
《武汉理工大学学报(交通科学与工程版)》
2012年第2期243-246,共4页
Journal of Wuhan University of Technology(Transportation Science & Engineering)
基金
国家自然科学基金项目(批准号:50876035
50906026)
中国博士点学科新进教师博士点基金项目(批准号:20070487093)
中国博士后科学基金项目(批准号:20100471165)资助
关键词
毛细相变流体回路
蒸发器
动量方程
启动特性
capillary loop with phase change
evaporator
momentum equation
start-up characteristic