绝缘子防冰过程中半导体硅橡胶涂层电阻的配置 被引量:5

Resistance Allocation Plan of Semiconducting Silicone Rubber Applied to Insulators for Anti-icing
下载PDF
导出
摘要 目前导线防覆冰技术已经相对成熟,而绝缘子的防覆冰方法仍处于实验室研究阶段,其中在绝缘子下表面涂覆半导体有机硅橡胶涂层的防覆冰方法已在人工气候室取得一定效果。为对半导体硅橡胶涂层电阻值的配置及相关的污闪问题进行研究,首先建立了基于热力学理论的绝缘子防冰热平衡模型,通过模型估算单片XP-70绝缘子涂层的电阻值,并在人工气候室内进行了防覆冰试验验证;重点讨论了电压、预染污方式对防冰效果的影响以及涂层对绝缘子污闪电压的影响。理论和试验结果表明:涂层电阻的范围在0.1~0-3MΩ以下时,涂层绝缘子具有较好的防冰效果,此结果可为中国输电线路及绝缘子防覆冰工作提供一定的指导。 The anti-icing and de-icing methods of insulator strings are still under laboratory studies, although many anti-icing technologies for overhead conductors have been relatively mature. The anti-icing method using semiconducting silicone rubber (SIR) coating applied to the bottom side of the insulators could get good results in a climate chamber. The configuration of the coating resistance and the subsequent pollution flashover problem were studied. A heating analytical method of insulators with semiconducting SIR was proposed. The resistance of the coating applied to the single XP-70 insulator was estimated. The anti-icing tests were carried out to verify the calculation results and the influence of the applied voltage and precontamination to the anti-icing performance was also discussed. The theoretical and experimental results show that the insulator would get a better anti-icing performance when the resistance is about 0.1-0.3MΩ, which can provide a guideline for anti-icing of transmission lines and insulators in China.
出处 《中国电机工程学报》 EI CSCD 北大核心 2012年第13期116-123,199,共8页 Proceedings of the CSEE
基金 国家自然科学基金项目(51077081 51177081) "十一五"国家科技支撑计划重大项目(2009BAA23B04)~~
关键词 半导体硅橡胶 防冰 电阻配置 泄漏电流 预染 污闪 semiconducting selection of resistance leakage pollution flashover silicone rubber anti-icing current precontamination pollution flashover
  • 相关文献

参考文献27

  • 1Farzaneh M, Kiernicki 2. Flashover problems caused by ice build up on insulators[J]. Electrical InsulationMagazine, 1995, 11(2): 5-17.
  • 2Hu Jianlin, Sun Caixin, Jiang Xingliang, et al. Flashover performance of pre-contaminated and ice-covered composite insulators to be used in 1000 kV UHV AC transmission lines[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(6): 1347-1356.
  • 3Fikke S M, Hanssen J E, Rolfseng L. Long range transported pollutants and conductivity of atmospheric ice on insulators[J]. IEEE Transactions on Power Delivery, 1993, 8(3).. 1311-1321.
  • 4Kawai M. AC flashover tests at project UHV on ice-coated insulators[J]. IEEE Transactions on Power Apparatus and Systems, 1970, 89(8): 1800-1804.
  • 5Charneski M D, Gaibrois G L, Whitney B F. Flashover tests of artificially iced insulators[J]. Power Engineering Review, 1982, 2(8): 17-18.
  • 6蒋兴良,卢杰,杜辕,苑吉河.间插布置绝缘子串的交流冰闪特性[J].中国电机工程学报,2009,29(10):12-16. 被引量:17
  • 7蒋兴良,王波,张志劲,胡建林,孙才新.串长及布置方式对高海拔覆冰绝缘子串直流冰闪电压的影响[J].中国电机工程学报,2008,28(3):1-5. 被引量:17
  • 8Farzaneh M. Atmospheric icing of power networks[M]. Netherlands: Springer, 2009: 229-265.
  • 9Horwill C, Davidson C C, Granger M. An application of HVDC to the de-icing of transmission lines[M]. New York: IEEE, 2006: 529-534.
  • 10Laforte J L, Allaire M A, Laflamme J. State-of-the-art on power line de-icing[J]. Atmospheric Research, 1998, 4'6(1-2): 143-158.

二级参考文献85

共引文献160

同被引文献60

引证文献5

二级引证文献30

相关作者