期刊文献+

Limits to foundation displacement of an extra high voltage transmission tower in a mining subsidence area 被引量:9

Limits to foundation displacement of an extra high voltage transmission tower in a mining subsidence area
下载PDF
导出
摘要 Given the background of a transmission tower erected on a particular mining subsidence area,we used finite element modeling to analyze the anti-deformation performance of transmission towers under a number of different load conditions,including horizontal foundation displacement,uneven vertical downward displacement,wind loads and icing conditions.The results show that the failure in stability of a single steel angle iron represents the limit of the tower given ground deformation.We calculated the corresponding limits of foundation displacements.The results indicate that compression displacement of the foundation is more dangerous than tension displacement.Under complex foundation displacement conditions,horizontal foundation displacement is a key factor leading to failure in the stability of towers.Under conditions of compression or tension displacement of the foundation,wind load becomes the key factor.Towers do not fail when foundation displacements are smaller than 1% (under tension) or 0.5% (under horizontal compression or single foundation subsidence) of the distance between two supports. Given the background of a transmission tower erected on a particular mining subsidence area, we used finite element modeling to analyze the anti-deformation performance of transmission towers under a number of different load conditions, including horizontal foundation displacement, uneven vertical downward displacement, wind loads and icing conditions. The results show that the failure in stability of a single steel angle iron represents the limit of the tower given ground deformation. We calculated the corresponding limits of foundation displacements. The results indicate that compression displace- ment of the foundation is more dangerous than tension displacement. Under complex foundation dis- placement conditions, horizontal foundation displacement is a key factor leading to failure in the stability of towers. Under conditions of compression or tension displacement of the foundation, wind load becomes the key factor. Towers do not fail when foundation displacements are smaller than 1% (under tension) or 0.5% (under horizontal compression or single foundation subsidence) of the distance between two supports.
出处 《International Journal of Mining Science and Technology》 2012年第1期13-18,共6页 矿业科学技术学报(英文版)
基金 National Natural Science Foundation of China(No.50004008) Xuzhou Power Supply Company and the Fundamental Research Funds for the Central Universities(No.2011QNB18) for their financial and technical support for this work
关键词 高压输电塔 地基位移 采煤沉陷区 基础位移 横向压缩 水平位移 建模分析 负载条件 Mining subsidence area Electricity transmission tower Foundation displacement limit Finite element analysis Limit state Stability failure
  • 相关文献

参考文献8

二级参考文献66

共引文献137

同被引文献69

引证文献9

二级引证文献33

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部