期刊文献+

110kV线路保护误动作分析及建议

Analysis and suggestions of misoperation on 110kV line protection
下载PDF
导出
摘要 通过对110kV并列运行双回线和双电源环网线路负荷侧保护在线路对侧母线出线故障时误动事例的分析,从改变运行接线方式、提高线路主保护配置及退出后备段保护3个方面提出解决措施,从而简化了负荷侧保护的整定配合及投退方案,提高了可靠性。结果表明:110kV线路配置光差保护,强化主保护功能,是电网多方式安全运行的必要保障。 Analyzes the example of 110 kV parallel operation two-way transmission line and dual power loop network load side protection misoperation when opposite side bus-bar outlet fault, puts forward the solution measures from three aspects: to change the mode of the operation connection, to enhance the main protection configuration of the transmission line and to exit the back-up protection, consequently simplifies the load-side protection setting matching and the switching scheme and increases reliability. The result shows that fiber differential protection allocated on 110 kV transmission line may strengthen main protection function, which is the necessary guarantee for muhimode operation of the power network.
出处 《宁夏电力》 2012年第2期25-28,49,共5页 Ningxia Electric Power
关键词 负荷侧保护 误动 纵差保护 多方式运行 load side protection misoperation longitudinal differential protection muhimode operation
  • 相关文献

参考文献2

二级参考文献2

  • 1DIdT584-2007.3kV-110kV电网继电保护装置运行整定规程[S].中国电力出版社,2008.
  • 2孙国凯,霍利民,柴玉华.电力系统继电保护[M].中国水利水电出版社,2002.

共引文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部