交流电场对复合绝缘子覆雾凇过程影响研究

Study on influence of AC electrical field on process of composite insulators covered-with rime
下载PDF
导出
摘要 绝缘子覆冰严重威胁输电线路的安全运行,而电场对输电线路绝缘子覆冰的影响不可忽视。以复合绝缘子FXBW-35/100为试品,在人工气候室内模拟自然覆冰条件,分析研究电场对复合绝缘子覆雾凇过程的影响。结果表明:电场对绝缘子覆雾凇的影响主要体现为对水滴的吸引作用和泄漏电流以及绝缘子表面各类放电现象的作用。电吸力的作用使得覆冰量与覆冰密度增加,泄漏电流以及绝缘子表面各类放电现象使得覆冰量与覆冰密度减小。随着外加电压的升高,绝缘子伞裙边缘、伞裙下表面以及芯棒背风面的雾凇明显增多,迎风面的雾凇全部出现下垂现象;带电覆雾凇时,雾凇密度较不带电时大;覆冰15 min时,冰重随电压的增长有一个先增加后减小的过程。 Icing on the insulators is one of the severe problems for external insulation of transmission lines and the influence of AC electrical field on the icing process of the transmission line insulators can't be neglected.As a result,experiment investigations are carried out on the FXBW-35/100 composite insulators in the artificial climate chamber of Chongqing University.The Influence of AC electrical field on process of composite insulators covered-with rime is studied.Based on the test results,it can be concluded that the influence of AC electrical appears mainly as the absorption,the leakage current and the discharge on the insulator.The absorption is the reason of the weight and density of the ice increasing.And the leakage current and the discharge on the insulator will reduce the weight and density of the ice.The amount of rime is great at the edge of the sheds,the upwind of the bottom-surface and the lee face of the core rod as the voltage rise.The rimes on energized at the upwind will droop.The weight of the ice will increase at first and then reduce with the increase of the voltage.
出处 《江西电力》 2012年第1期20-24,共5页 Jiangxi Electric Power
基金 国家自然科学基金资助项目(50577070)
关键词 覆冰 复合绝缘子 电场 雾凇 icing composite insulators electric field rime
  • 相关文献

参考文献13

二级参考文献42

  • 1蒋兴良,武利会,司马文霞,舒立春,孙才新.低气压下XZP/XZWP4-160直流绝缘子覆冰闪络特性研究[J].中国电机工程学报,2004,24(6):111-115. 被引量:29
  • 2司马文霞,蒋兴良,武利会,舒立春,孙才新.低气压下覆冰染污10kV合成绝缘子直流电气特性[J].中国电机工程学报,2004,24(7):122-126. 被引量:71
  • 3舒立春,孙才新,顾乐观.覆冰、低气压下染污绝缘子的交流闪络特性[J].高电压技术,1995,21(2):14-18. 被引量:17
  • 4张志劲,蒋兴良,马俊,胡建林,梁瑜.工作电压下110kV交流绝缘子串覆冰特性研究[J].中国电机工程学报,2006,26(4):140-143. 被引量:41
  • 5蒋兴良 易辉.输电线路覆冰及防护[M].北京:中国电力出版社,2001..
  • 6Shu L, Sun C, Gu L, et al. Influence of low atmospheric pressure and ice-covered on performance of polluted composite insulator[C]. IEE of Japan Power& Energy, Japan, 1994.
  • 7ShuL, SunC, GuL, et al. A study on flashover characteristics of polluted composite insulator under acid fog conditions[C]. Proceeding of the 9th ISH, Graz, Austria, 1995.
  • 8Farzaneh M, Zhang J. Behavior of DC arc discharge on ice surface[C]. Proceedings of 8th international workshop on the atmospheric icing of structure, Iceland, 1998.
  • 9S Cai-xin, J Xing-liang, S Wen-xia, et al. Study of flashover performance and voltage correction of DC insulator in icing districts of altitude of 2500m and below[C]. Proceedings of 10th IWAIS, Brno,Czech Repubic, 2002.
  • 10Jiang Xingliang, Sun Caixin, Sima Wenxia, et al. AC flashover performance and voltage correction of 27.5 and 110 kV iced composite insulator at atmospheric pressure of 4000~5500m high altitude districts[C]. IEEE Powercon'2002, Kunming, China, 2002.

共引文献433

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部