摘要 输电线路转角塔角度如果采用超限水平档距,在转角度数不大于上限的情况下,可以通过转角度数的余度来折算水平档距。具体计算时,采用折减系数的方法,忽略挂线点垂直荷载变化和纵向水平荷载的影响,利用转角塔挂线点水平荷载相等的原则,将输电线路转角塔角度折算成超限水平档距。该方法应用于实际工程中,可达到节约成本的目的。 If transfinite horizontal span is adopted for corner tower angle of transmission line, and turn angle is not larger than upper limit of next angle, horizontal span can be converted to redundancy angle of horizontal span. When doing detailed calculation, specific calculation method by means of reduction factor will be utilized, ignoring influence of hung perpendicular load change and impact of the vertical load level. Using principle of horizontal load equal to comer tower hung point horizontal load equal, angle of comer tower for transmission line can be converted into transfinite horizontal span. If it is applied to engineering practice, cost savings will be realized.
出处 《内蒙古电力技术》 2012年第2期57-59,共3页 Inner Mongolia Electric Power
关键词 输电线路转角塔 水平档距 折算档距 水平荷载 转角 corner tower of transmission line horizontal span converted span horizontal loads corner
  • 相关文献

参考文献3

  • 1中国电力企业联合会.GB 50545-2010.110 kV-750 kV架空输电线路设计规范[S].北京:中国计划出版社,2010.
  • 2中华人民共和国住房和城乡建设部.GB50009-2001建筑结构荷载规范[s].北京:中国建筑工业出版社,2006.
  • 3国家电网公司基建部.国家电网公司输变电工程通用设计:500kV(330kV)输电线路分册[S].北京:中国电力出版社,2011.