摘要 由于架空线和海底电缆的波阻抗不同,基于双端定位原理的行波故障定位装置在线-缆混合输电线路中无法发挥作用。根据海南联网工程的需要,开发了分布式行波故障定位系统。通过在架空线和海底电缆交界处安装行波故障定位监测终端,记录故障行波方向、GPS时间和行波在不同介质中的传播速度,从而实现故障的区间定位和精确定位。该系统应用于海南联网工程500 kV福港线,其运行情况显示系统工作是安全、可靠的。 Due to the discrepancy of wave impedances between overhead lines and submarine cables,traveling wave fault location based on the dual side positioning principle can not adjust to the cable hybrid transmission lines.According to the needs of Hainan’s networking project,the distributed traveling wave fault location system is developed.Through installing monitoring terminals of traveling wave fault location at the junction of overhead lines and submarine cables,traveling wave direction,GPS time,and wave propagation velocity in different media can be recorded,and thus achieving fault interval mapping and precise positioning.The system is applied to 500 kV Fushan-Gangcheng line,known as Hainan’s networking project,whose operation verifies the system’s safty and reliability.
作者 张富春 高峰
出处 《南方电网技术》 2012年第2期112-115,共4页 Southern Power System Technology
关键词 架空线 海底电缆 故障定位 overhead lines submarine cables fault location
  • 相关文献

参考文献7

二级参考文献22

共引文献117

同被引文献62

  • 1金作林,陈小月,文习山,郭卫,任志刚.海上风电场220 kV海底长电缆送出线工频及操作过电压研究[J].电瓷避雷器,2020(1):47-53. 被引量:29
  • 2黄叶.充油电缆介损超标处理[J].电工技术,2002(2):52-53. 被引量:1
  • 3陈凌云,朱熙樵,李泰军.海南联网工程海底电缆的选择[J].高电压技术,2006,32(7):39-42. 被引量:36
  • 4羊初发.基于EMD的时频分析与滤波研究[D].四川成都:电子科技大学,2006,28-42.
  • 5田培根,刘海军,周学军,等.锚害对海底光缆线路的安全威胁及应对措施研究[C]//中国通信学会.中国通信学会2009年光缆电缆学术年会论文集.成都:中国通信学会,2009.
  • 6MAUGHAN S M, KEE H H, NEWSON T P. Simultaneous distributed fibre temperature and strain sensor using microwave coherent detection of spontaneous Brillouin backscatter [ J l- Measurement Science and Technology, 2001 (12) : 834 - 842.
  • 7HIROHUMI T, OSAMU F, KENICHI Y, et al. 66 kV XLPE submarine cable with optical fiber sensors to detect anchor dam- age and defacement of wire armor [ J 1. IEEE Transactions on Power Delivery, 1995, 10(4) : 1718 - 1723.
  • 8NISHIMOTO T, MIYAHARA T, Takehana H, et al. Develop- ment of 66 kV XLPE submarine cable using optical fiber as a mechanical damage detection sensor I J ]. IEEE Transaction on Power Delivery, 1995, 10(4) : 1711 - 1737.
  • 9HVIDSTEN S, FLODEN R, OLAFSEN K, et al. Long term e- lectrical properties of XLPE cable insulation system for subsea applications at very high temperatures I C ]//IEEE. 2005 Annual Report Conference on Electrical Insulation and Dielectric Phe- nomena, Nashville, TN, USA, Oct 16 - 19, 2005. Nashville: IEEE, 2005 : 265 - 268.
  • 10EPACHER E. Two step degradation of high density polyethylene during multiple extrusion E J]. Journal of Applied Polymer Sci- ence, 1999, 74, 1596-1605.