期刊文献+

伞裙结构对330kV复合绝缘子交流覆冰特性影响 被引量:2

Effect of Shed Structure Upon 330 kV Composite Insulator AC Icing Character
下载PDF
导出
摘要 通过在人工气候室对设计的5种不同伞形结构的330 kV复合绝缘子进行大量的人工覆冰闪络试验,研究了伞形结构对复合绝缘子覆冰状态及50%覆冰闪络电压的影响。试验结果表明,相同覆冰程度下,不同伞型结构复合绝缘子的覆冰状态有明显的差异,优化复合绝缘子的伞形结构,合理布置大伞,可以使覆冰闪络电压提高50%。研制了330 kV防冰闪复合绝缘子,并在电力系统中大量使用,运行效果良好。 Large number of artificial icing flashover test is conducted for the composite insulator with 5 different sheds in the artificial climate chamber. The effect of shed structure upon composite insulator icing & 50% icing flashover voltage is studied. The test showed that the 5 shed structure composite insulators'icing is rather different under same icing. Optimization of shed structure of composite insulator & reasonable arrangement of shed can improve 50% of icing flashover voltage. 330kV icing flashover prevention composite insulator is researched and applied in power system, and obtain good operation effect.
出处 《陕西电力》 2012年第5期43-47,共5页 Shanxi Electric Power
关键词 伞形结构 复合绝缘子 覆冰 闪络电压 shed structure composite insulator icing flashover voltage
  • 相关文献

参考文献3

二级参考文献27

  • 1张俊锋.复合绝缘子在多雷地区的应用[J].福建电力与电工,2003,23(4):8-9. 被引量:7
  • 2梁旭明,蒲春雨,寻凯,宿志一,范建斌,陈原,张锐,黄梓容.500kV线路复合绝缘子鸟啄情况调查及原因分析[J].电网技术,2005,29(22):19-23. 被引量:35
  • 3钱之银,包建强,吴明祥.进口合成绝缘子断裂原因分析[J].高电压技术,2004,30(5):34-36. 被引量:22
  • 4殷禹,梁曦东,周远翔,毛苏春,李雪松.转轮法试验中硅橡胶合成绝缘子损坏现象的研究[J].电网技术,2004,28(19):68-71. 被引量:24
  • 5梁英,李成榕,丁立健,屠幼萍,赵林杰,杨堃,刘富家,杨铁军.合成绝缘子材料的TSC试验研究[J].电工技术学报,2006,21(2):13-16. 被引量:15
  • 6孙才新 蒋兴良 舒立春 等(Sun Caixin Jiang Xingliang Shu Lichun et al).高海拔、污秽、覆冰环境下超高压线路绝缘子交直流放电特性及闪络电压校正研究[J]..
  • 7Shu L, Sun C, Gu L, et al. Influence of low atmospheric pressure and ice-covered on performance of polluted composite insulator[C]. IEE of Japan Power& Energy, Japan, 1994.
  • 8ShuL, SunC, GuL, et al. A study on flashover characteristics of polluted composite insulator under acid fog conditions[C]. Proceeding of the 9th ISH, Graz, Austria, 1995.
  • 9Farzaneh M, Zhang J. Behavior of DC arc discharge on ice surface[C]. Proceedings of 8th international workshop on the atmospheric icing of structure, Iceland, 1998.
  • 10S Cai-xin, J Xing-liang, S Wen-xia, et al. Study of flashover performance and voltage correction of DC insulator in icing districts of altitude of 2500m and below[C]. Proceedings of 10th IWAIS, Brno,Czech Repubic, 2002.

共引文献296

同被引文献33

引证文献2