期刊文献+

溶液除湿蒸发冷却系统在厦门地区的节能潜力 被引量:6

Energy Saving Potential of Liquid Desiccant Evaporative Cooling System in Xiamen
下载PDF
导出
摘要 根据厦门地区的气候条件和相关空调设计参数,将溶液除湿蒸发冷却系统(LDECS)的能耗及相关特性与传统一次回风空调系统进行了对比。结果表明,LDECS较传统一次回风系统可节约21.1%的运行能耗,并且环保及送风空气品质好,在厦门地区应用该系统具有较大的节能潜力。 According to Xiamen weather conditions and design parameters related to air conditioning,energy consumption and related characteristics of the liquid desiccant evaporative cooling system(LDECS) were compared with traditional air conditioning system.The result shows that,LDECS than the traditional system can save energy consumption of 21.1%,environmental protection and air quality is good,the application of the system in Xiamen has great potential for energy savings.
出处 《流体机械》 CSCD 北大核心 2012年第5期67-70,共4页 Fluid Machinery
基金 福建省青年人才创新项目(2009J05127) 福建省教育厅项目(JK2010033)
关键词 蒸发冷却 溶液除湿 空调系统 节能 evaporative cooling liquid desiccant air conditioning systems energy saving
  • 相关文献

参考文献13

二级参考文献209

共引文献368

同被引文献70

引证文献6

二级引证文献20

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部