阐述了LW 11- 2 2 0W断路器气动机构分闸阀存在的特殊问题 ,从理论上分析了分闸阀积水、锈蚀从而造成断路器拒分的原因 ,并提出一些建议措施。
This paper addresses a special failtobreak problem existing in the pneumatic actuator of Type LW11220W circuit breaker. From theoretical analysis, the authors believe that water accumulation and corrosion in circuit breaking valve are the causes of the problem. Some suggestions for solving the problem are proposed.
出处
《河北电力技术》
2000年第1期43-44,共2页
Hebei Electric Power
关键词
断路器
气动机构
分闸阀
积水锈蚀
拒分
circuit breaker
pneumatic actuator
circuit break valve
water accumulation and corrosion
failtobreak