摘要
介绍了在配电网中消除谐波的方法,提出了基于曲折移相的无电容拓扑零序滤波器。投入滤波器前后的测量结果显示,投入滤波器后基波不平衡电流约降到原来的1/6—1/3,3次谐波电流约降到原来的1/3,9次谐波电流约降到原来的1/9~1/5。
Introducing the harmonic elimination methods in distribution networks, this paper presents a topological zero-sequence filter without capacitor based on zigzag phase-shifting. The comparison of measurement results without and with the filter shows that the fundamental imbalance current as with the filter is down to 1/6- 1/3 of that as without the filter, and the 3rd harmonic current is down to 1/3 while the 9th harmonic current is down to 1/9 - 1/5.
出处
《南方电网技术》
2012年第A01期57-60,共4页
Southern Power System Technology
关键词
配电网
谐波污染
消除
distribution network
harmonic pollution
elimination