摘要
以某企业为测试对象,对其谐波治理前后的变压器损耗进行测量,经治理后线路谐波电流总畸变率下降17.52%,变压器损耗减少20.4%,谐波治理能有效降低变压器损耗,节能效果显著。
An enterprise in Jiangsu as the test object,we measured the loss of transformer before and after the harmonic treatment.As we measured,the harmonic current distortion rate dropped 17.52%, loss of the transformer is reduced 20.4% after the harmonic treatment. The harmonic control can effectively reduce the loss of transformer, energy-saving effect of significantly.
出处
《上海节能》
2012年第6期42-44,共3页
Shanghai Energy Saving
关键词
谐波治理
变压器损耗
工程实测
harmonic treatment
loss of the transformer
project example