期刊文献+

500kV直流输电线路耐张线夹断裂的原因分析 被引量:36

Analysis on Cracking Failure of Strain Clamp on 500 kV DC Transmission Line
原文传递
导出
摘要 对某500kV直流输电线路失效的耐张线夹进行了宏观检查、尺寸测量、射线检验以及现场模拟试验,并结合规范对试验结果进行了分析,指出压接工艺不当是线夹断裂的主要原因。该分析对耐张线夹的液压施工以及确保输电线路安全运行具有借鉴意义。 According to the standard, the strain clamp with cracking failure on 500 kV DC transmission line was investigated by the means of macroscopic examination, measured on the margins, ray inspection, chemical analysis and field test. The results show that the main reason of cracking failure is the improper process of pressure contact technique, which presents references for the strain clamp's hydraulic construction and has significance meaning for the safe operation of transmission lines.
出处 《电力建设》 2012年第7期82-85,共4页 Electric Power Construction
关键词 耐张线夹 压接工艺 断裂 strain clamp pressure contact technique cracking failure
  • 相关文献

参考文献13

二级参考文献27

  • 1高建华,施天明.影响导线接头液压握着力的因素分析[J].电力建设,1993,14(9):39-44. 被引量:3
  • 2赵凤华,郭德耀,刘纯智.400/50ND钢锚断裂分析[J].东北电力学院学报,1996,16(2):23-27. 被引量:2
  • 3左晓文.2006年发电机组运行可靠性分析[J].电力设备,2007,8(7):83-88. 被引量:1
  • 4SDJ 220-87架空送电线路导线及避雷线液压施工工艺规程[S].
  • 5SDJ226-1987架空送电线路导线及避雷线液压施工工艺规程[S].北京:水利电力出版社,1987.
  • 6CB50233-2005110-500kV架空送电线路施工及验收规范[S].北京:中国计划出版社,2005.
  • 7SDJ226-87架空送电线路导线及避雷线液压施工工艺规程[S].北京:水利电力出版社,1987.
  • 8GB/T1179—2008圆线同心绞架空导线[S].北京:中国标准出版社.2008.
  • 9GB/T2314-2008电力金具通用技术条件[S].北京:中国标准出版社,2008.
  • 10DL/T683-1999电力金具产品型号命名方法[S].北京:中国电力出版社,1999.