摘要
根据智能大厦建筑体、内部设备和该地区年平均雷电日数,分别计算出建筑物年预计雷击次数、可接受的最大年平均雷击次数、防雷装置拦截效率,计算出该智能大厦的雷电防护等级,并以此为依据对电源、信号系统设置SPD保护和接地等电位连接,为智能办公大厦综合防雷工程设计提供参考依据。
According to intelligent building construction body,interior equipment and the local annual average lightning days, the annual expected buildings-struck numbers, the maximum acceptable annual average lightning numbers, interception efficiency of lightning protection devices and the lightning protection level of the Intelligent Building were calculated.
出处
《气象研究与应用》
2012年第2期114-117,共4页
Journal of Meteorological Research and Application
关键词
智能大厦
电子信息系统
雷电灾害风险评估
综合防雷技术应用
intelligent Building
electronic information system
lightning disaster risk assessment
applicationof lightning protection technology