110kV瓦-隆线脱冰跳跃故障原因分析及治理

Cause analysis and treatment on the conductor sleeting jump fault in 110 kV Wating-Longde power transmissin line
下载PDF
导出
摘要 针对110 kV瓦-隆线脱冰跳跃故障进行原因和特性分析,分别计算了(45~46)号塔,(46~47)号塔2个档段脱冰跳跃引起的档中最大振幅,在此基础上,借鉴国网公司治理架空线舞动的经验,设计了相间间隔棒的布置位置,给出了采用相间间隔棒进行治理的措施。运行情况表明:该治理措施取得了预期的效果。 Aiming at the conductor sleeting jump fault in 110 kV Wating-Longde power transmissin line, analyzes causes and characteristics of the fault, calculates the maximum oscillation amplitude of line between No. 45 and No. 46 tower and between No.46 and No.47 tower caused by the conductor sleeting jump, references the experience of the state grid treated the oscillation of overhead line, designs the collocation place of phase space stick, puts forward the treatment measures of using the phase space stick. The operation result shows that the treatment measures obtain the expected effect.
出处 《宁夏电力》 2012年第3期32-35,39,共5页 Ningxia Electric Power
关键词 瓦隆线 架空线 脱冰跳跃 不平衡张力 相间间隔棒 Wating-Longde power transmissin line overhead line conductor sleeting jump unbal- anced tension phase space stick
  • 相关文献

参考文献2

二级参考文献17

  • 1蒋兴良,马俊,王少华,孙才新,舒立春.输电线路冰害事故及原因分析[J].中国电力,2005,38(11):27-30. 被引量:168
  • 2刘万顺.电力系统故障分析[M].北京:水利电力出版社,1983..
  • 3程应堂.送电线路金具的设计安装实验和应用[M].北京:水利电力出版社,1989..
  • 4Kalman T, Farzaneh M, McClure G. Numerical analysis of the dynamic effects of shock-load-induced ice shedding on overhead ground wires[J]. Computers and Structures, 2007, 85(7-8): 375-384.
  • 5Wang J, Lilien J L. Overhead electrical transmission line galloping: A full multi-span 3-DOF model, some applications and design recommendations[J]. IEEE Transactions on Power Delivery, 1998, 13(3): 909-916.
  • 6McClure G, Lapointe M. Modeling the structural dynamic response of overhead transmission lines[J]. Computers and Structures, 2003, 81(8-11): 825-834.
  • 7Barbieri N, De Souza Junior O H, Barbieri R. Dynamical analysis of transmission line cables, Part 1 - Linear theory[J]. Mechanical Systems and Signal Processing, 2004, 18(3): 659-669.
  • 8Rawlins C B. Long span problem in the analysis of conductor vibration damping[J]. IEEE Transactions on Power Delivery, 2000, 15(2): 770-776.
  • 9Munaswamy K, Haldar A. Self-damping measurements of conductors with circular and trapezoidal wires[J]. IEEE Transactions on Power Delivery, 2000, 15(2): 604-609.
  • 10Richardson A S Jr. Vibration damping required for overhead lines [J]. IEEE Transactions on Power Delivery, 1995, 10(2): 934-940.

共引文献75

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部