期刊文献+

配管长度及分歧管间距对多联式空调性能的影响 被引量:1

The influence of pipe length and pipe-connector spacing on performance in multi-connected air-condition system
下载PDF
导出
摘要 通过实验的方法,研究了变负荷工况下配管长度与分歧管间距对多联式空调系统的能效比(EER)及冷量不平衡率的影响.结果表明,配管长度过长造成EER下降和冷量衰减,影响室内机的放冷量,配管长度不应超过162 m;随着分歧管间距增加,系统的EER及制冷量不平衡率急剧下降,同时分歧管间距对系统性能的影响远大于配管长度. Through a testing, the influence of different cooling load on EER and unbalance rate of refrigera- ting capacity in multi-conneted air-condition system was studied. Influence of pipe length and pipe-connec- tor spacing on performance of the unit was researched based on different cooling load. The results showed that the EER and refrigerating capacity was decreasing as the pipe length increased to 162 m and pipe-con- nector spacing increased;the influence of pipe-connector spacing on performance of multi-connected air- condition system was much larger than pipe length.
出处 《郑州轻工业学院学报(自然科学版)》 CAS 2012年第4期33-35,共3页 Journal of Zhengzhou University of Light Industry:Natural Science
基金 河南省教育厅科学技术研究项目(2011B120006)
关键词 多联式空调系统 能效比 配管长度 分歧管间距 multi-connected air-condition system energy efficiency ratio pipe length pipe-connector spac- ing
  • 相关文献

参考文献7

二级参考文献30

共引文献42

同被引文献5

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部