摘要 通过对1起110 kV线路终端无间隙复合外套金属氧化物避雷器爆炸事故同批次试品的解体检查试验,指出整体密封性能较差导致运行受潮,是加速了电阻片老化的主要原因;针对线路终端避雷器运行条件和运行管理的薄弱环节,提出运行管理和试验维护建议。 According to disassembly analysis and test on the gapless composite-coat metal oxide surge arresters among the same batch in an explosion accident of 110 kV line terminals, it is considered that poor sealing condition caused the operation wetting, and is the main reason for the accelerated aging of the resistors; some suggestions of operating management and testing maintenance are proposed for the operating conditions of the surge arrester at the line terminals and the weak links of the operating management.
作者 李谦 汤振鹏
出处 《电瓷避雷器》 CAS 北大核心 2012年第4期49-53,共5页 Insulators and Surge Arresters
关键词 金属氧化物避雷器 解体分析 受潮 电阻片 老化 运行管理 zinc oxide arrester disassembly analysis wetting resistor aging operation maintenanc