局部放电射频信号与其视在放电量的关联分析(英文) 被引量:7

Relationship Between PD Measured with RF Techniques and Apparent Charge Quantity
下载PDF
导出
摘要 Radio frequency(RF) measurement has become a hot issue for partial discharge detection.However,its application is hampered by the difficulty to establish a relationship between the RF measurements data and apparent discharge quantity.In this paper,on the basis of an experimental model of metal protrusion,the relationship between the results of RF measurement and pulse current method(IEC 60270) was investigated.The energy,double integration,peak voltage,peak-peak voltage and the area of RF signals were plotted versus either the apparent discharge quantity or the square of the apparent discharge quantity in order to evaluate the optimal regression curve.At the same time,the impact of voltage and the distance between protrusion and plate were also investigated.The results indicate that the optimal match to a linear regression curve can be gained by plotting the RF signal energy versus the square of the apparent discharge quantity.The variation of voltage has no significant impact on the regression curve;that is,data from different voltages match one line.However,when the distance between protrusion and plate is changed,the slope of the regression curve changes accordingly;the same energy corresponds to a bigger discharge quantity.The results are significant enough to be applied in the estimation of the discharge quantity by measuring RF partial discharge signals. Radio frequency(RF) measurement has become a hot issue for partial discharge detection.However,its application is hampered by the difficulty to establish a relationship between the RF measurements data and apparent discharge quantity.In this paper,on the basis of an experimental model of metal protrusion,the relationship between the results of RF measurement and pulse current method(IEC 60270) was investigated.The energy,double integration,peak voltage,peak-peak voltage and the area of RF signals were plotted versus either the apparent discharge quantity or the square of the apparent discharge quantity in order to evaluate the optimal regression curve.At the same time,the impact of voltage and the distance between protrusion and plate were also investigated.The results indicate that the optimal match to a linear regression curve can be gained by plotting the RF signal energy versus the square of the apparent discharge quantity.The variation of voltage has no significant impact on the regression curve;that is,data from different voltages match one line.However,when the distance between protrusion and plate is changed,the slope of the regression curve changes accordingly;the same energy corresponds to a bigger discharge quantity.The results are significant enough to be applied in the estimation of the discharge quantity by measuring RF partial discharge signals.
出处 《高电压技术》 EI CAS CSCD 北大核心 2012年第8期1828-1833,共6页 High Voltage Engineering
基金 supported by National Basic Research Program of China(973 Program)(2009CB724506) National Natural Science Foundation of China(50977095)
关键词 局部放电 射频信号 放电量 高电压技术 radio frequency partial discharge discharge quantity pulse current method energy linear regression curve
  • 相关文献

参考文献16

  • 1Hikita M, Ohtsuka S, Matsumoto S. Recent trend of the partial discharge measurement technique using the UHF electromagnetic wave detection method [J].IEEJ Transactions on Electrical and Electronic, 2007, 2(1): 504-509.
  • 2Judd M D, Farish O, Hampton B F. Excitation of UHF signals by partial discharges in GIS[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1996, 3(4): 213-228.
  • 3Bell R, Charlson C, Halliday S P, et al. High voltage onsite commissioning tests for gas-insulated substations using UHF partial discharge detection[J]. IEEE Transactions on Power Delivery, 2003, 18( 4).. 1187-1191.
  • 4Tang J, Zhou Q, Tang M, et al. Study on mathematical model for VHF partial discharge of typical insulated defects in GIS[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(1), 30-37.
  • 5Reid A J, Judd M D, Stewar B G, et al. Identification of multi- ple defects in solid insulation using combined RF and IEC60270 PD measurement[C]//9th IEEE International Conference on Solid Dielectrics. Winchester, UK: IEEE, 2007: 585-588.
  • 6Reid A J, Judd M D, Stewar B G, et al. Correlation between RF energy and IEC60270 apparent charge for selected partial discharge source geometries[C]//15th International Symposium on High Voltage Engineering. Ljubljana, Slovenia: ISH, 2007.
  • 7Stewart B G, Reid A J, Judd M D, et al. UHF and IEC60270 correlation analysis of radiated frequency band measurements on resin insulation void samples [C]//2007 Electrical Insulation Conference and Electrical Manufacturing Expo. Nashville, USA: IEEE, 2007: 138-141.
  • 8Sellars A G, MacGregor S J, Farish O. Calibrating the UHF technique of partial discharge detection using a PD simulator[J].IEEE Transactions on Dielectrics and Electrical Insulation, 1995, 3(4): 46-53.
  • 9Koek N, Coric B, Pietseh R. UHF PD detection Jn gas-insulated switchgear--Suitability and sensitivity of the UHF method in comparison with the IEC 270 method[J]. IEEE Electrical Insu- lation Magazine, 1996, 12(6): 20-26.
  • 10Reid A J, Yang L, Judd M D, et al. An integrated measurement strategy for simultaneous fault identification: Combining the UHF and IEC60270 techniques [C] // 14th International Symposium on High Voltage Engineering. Beijing, China: ISH, 2005.. 394.

同被引文献92

引证文献7

二级引证文献100

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部