期刊文献+

风电场出线两端无功电能计量不一致问题分析 被引量:1

Reactive Energy Measurement Inconsistent of Wind Farm Double-line Ends
下载PDF
导出
摘要 近年来,内蒙古自治区风电的大规模接入给电网电能计量带来一定的影响,各风电场均出现线路两端无功电能计量不一致的问题,影响交易双方结算。通过试验研究发现,由于风电场大部分时间处于低负荷运行状态,线路输送功率远远小于线路的自然功率,线路的感性无功功率远小于容性无功功率,线路基本不消耗无功功率,而是输出容性无功功率,因此导致风电场两端无功电量值相差较大。提出了风电场安装无功补偿装置时容量的配置原则。在无功补偿容量配置合理的情况下,只要交易双方划清损耗的归属,便可以实现准确的结算。 In recent years, the wind power of the Inner Mongolia Autonomous Region Js large-scale access to power measurement to bring certain influence, the wind farms have two ends of a line of reactive energy measurement inconsistency problem, affecting both parties to the transaction settlement. It is found by experiments, due to wind electric field in the low load running status most of the time, transmission power is far less than the line of natural power, line reactive power is far less than the capacitive reactive power, the basic lines do not consume reactive power, but the output capacitive reactive power, thus leading to reactive power of wind farm at both ends value of difference. Proposed wind farm installation of reactive power compensation device capacity allocation principle. In the reactive power compensation capacity configuration reasonable under the circumstances, as long as both parties to draw the loss of home, then can realize the accurate billing.
出处 《内蒙古电力技术》 2012年第4期14-18,共5页 Inner Mongolia Electric Power
关键词 风电场 无功补偿 无功电能 计量 线路自然功率 容性无功功率 wind farm reactive compensation reactive power measurement line natural power capacitive wattless power
  • 相关文献