期刊文献+

六氟化硫分解物检测技术的应用 被引量:6

Application of Sulfur Hexafluoride Decomposition Products Detection Technique
下载PDF
导出
摘要 介绍了六氟化硫(SF6)电气设备分解物的检测方法和常见的故障类别。通过对蒙西电网某500 kV变电站500 kV断路器和110 kV变电站GIS设备进行SF6气体分解物(包括SO2、H2S、CO等)的检测实例分析,认为应用SF6分解物检测技术能够准确、迅速、方便地判断出SF6电气设备内部存在的放电故障,并制定了内蒙古电网SF6电气设备分解物的检测周期和指标,以指导SF6电气设备的安全运行。 The paper introduced the detection of sulfur hexafluoride (SF6) decomposition products in electrical equipment and common fault types. By detection on SF6 decomposition products in certain Inner Mongolia Power Grid 500 kV substation, 500 kV circuit breaker and 110 kV substation GIS equipment (including SO2, H2S, CO, etc.), determining the discharge failure inside of SF6 electrical equipment accurately, quickly and easily. Meanwhile, make the detection cycle and index for sulfur hexafluoride decomposition products of Inner Mongolia network to guide safe running of SF6 electrical equipment.
出处 《内蒙古电力技术》 2012年第4期80-83,共4页 Inner Mongolia Electric Power
关键词 SF6气体 分解物检测 SF6电气设备 故障诊断 检测周期 SF6 detection technique of decomposition products SF6 electrical equipment fault diagnosis detecting period
  • 相关文献

参考文献4

  • 1游荣文,潘腾.应用分解产物含量诊断SF6电气设备内部故障[c]//中国电力企业联合会.2009年全阂输变电设备状态检修技术交流研讨会论文集,北京:巾国电力出版社,2009:868—876.
  • 2电力行业高压开关标准化委员会.GB/T8905--2008六氟化硫电气设备中气体管理和检测导则(报批稿)[S].北京:[s.n.],2008.
  • 3国家电网公司.(2010)434号文关于认真做好迎峰度夏设备隐患排查治理工作的通知[S].北京:[s.n.],2010:29.
  • 4游荣文,黄逸松.基于SO_2、H_2S含量测试的SF_6电气设备内部故障的判断[J].福建电力与电工,2004,24(2):15-16. 被引量:37

二级参考文献1

共引文献36

同被引文献62

  • 1吕小虎,赵贵文.光声光谱法及其应用[J].分析仪器,1993(2):37-41. 被引量:6
  • 2申强,孙亮,仲伟涛,孟强.SF_6断路器在北方高寒地区的选择与应用[J].黑龙江电力,2004,26(6):425-427. 被引量:5
  • 3王艳秋,蒋志刚.户外SF_6断路器在严寒地区可靠运行[J].宁夏电力,2005(C00):92-94. 被引量:5
  • 4Tang J, Liu F, Zhang X X, et al. Partial discharge recognition through an analysis of SF6 decomposition products part 1 : de composition characteristics of SF6 under four different partial discharges[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(1): 29-36.
  • 5Beyer C, Jenett H, Klockow D. Influence of reactive SF, gases on electrode surfaces after electrical discharges under SF6 atmos phere[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2000, 7(2): 234 240.
  • 6IEC 60480:2004 Guidelines for the checking and treatment of sulfur hexafluoride (SF6) taken from electrical equipment and specification for its reuse[S], 2004.
  • 7Rothman I. S, Barbe A, Gordon I E, et al. The HITRAN 2008 molecular spectroscopic database[J]. Journal of Quanti tative Spectroscopy & Radiative Transfer, 2009, 110(9/10) : 533 572.
  • 8Webber M E. Diode laser measurements of NHs and CO2 for eornbustion and bioreactor applications[D]. Stanford, USA: Stanford University, 2001.
  • 9Bernath P F. Spectra of atoms and molecules[M]. Oxford, USA: Oxford University Press, 2005: 62.
  • 10Vandaele A C. Hermans C, Fally S, et al. Absorption cross- sections of NO2: simulation of temperature and pressure effects [J]. Journal of Quantitative Spectroscopy & Radiative Trans fer, 2003, 76(3): 373-391.

引证文献6

二级引证文献25

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部