35kV系统双母线TV二次电压非正常并列事故原因分析及防范措施 被引量:5

Cause Analysis and Preventive Measures of TV Secondary Voltage Abnormal Concatenation in 35 kV Double-bus System
下载PDF
导出
摘要 针对35 kV系统双母线电压互感器二次电压切换不成功造成插件烧毁的故障,结合电压切换原理,分析了事故原因是由于刀闸辅助接点不通,使双位置继电器不能可靠复归,造成两TV二次电压非正常并列,引发事故。提出应尽量避免双母线分列运行,加强对刀闸辅助接点的维护以及考虑采用单位置继电器等防范措施。 For the fault of plug-burning result from voltage transformer secondary voltage switch unsuccessful in 35 kV double-bus system, combining of the voltage switch principle, the paper analyzed the cause of the fault, which is disconnected switch auxiliary contacts connected failure, results in the two position relay can't return reliably and the two voltage transformers secondary voltage non-normal concatenation, and than leaded to the fault. In the paper, some preventive measures were proposed finally, preventing from the double-bus separated operation, improving maintain of the disconnected switch auxiliary contacts and considering of using the single position relay.
机构地区 乌兰察布电业局
出处 《内蒙古电力技术》 2012年第4期104-106,共3页 Inner Mongolia Electric Power
关键词 35kV系统 双母线 电压切换 单相接地 二次电压并列 双位置继电器 35 kV system double-bus voltage switch single phase grounding secondary voltage concatenation two position relay
  • 相关文献

参考文献3

二级参考文献6

共引文献24

同被引文献19

  • 1DL/T5149-2001,220-500kV变电所计算机监控系统设计技术规程[S],2001.
  • 2广东省电力调度中心.广东省电力系统继电保护反事故措施及释义(2007版)[M].北京:中国电力出版社,2008.
  • 3国家电力调度通信中心.电力系统继电保护典型事故分析[M].中国电力出版社,2003.
  • 4王善祥,等.NSR600R系列保护测控装置技术说明书[Z].南京:国电南瑞科技股份有限公司,2004
  • 5Q/GD001.1119.1-2005.广东电网110-220kV变电站自动化系统技术规范[S].
  • 6Q/GD001.1122012007.广东电网500kV变电站自动化系统技术规范[S].
  • 7朱若松.zYQ一824电压切换箱使用说明书[Z].许昌:许继电气股份有限公司,2008.暴.
  • 8立勇.JFZ-32Q电压并列箱说明书[Z].北京:北京四方继保自动化股份有限公司,2008.
  • 9宗秀红,王炼,王世祥.电压切换回路的隐患分析[J].电力系统保护与控制,2008,36(20):69-71. 被引量:23
  • 10刘冠祥,韩东泊,房民.电压互感器二次并列回路改进[J].山东电力技术,2009,36(4):28-30. 被引量:3

引证文献5

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部