期刊文献+

ZS-126/4型支柱绝缘子的交流覆冰闪络特性 被引量:4

AC Icing Flashover Performance of Post Insulator ZS-126/4
下载PDF
导出
摘要 为研究支柱绝缘子交流覆冰闪络特性,以110kV支柱绝缘子ZS-126/4为试品,在大型多功能人工气候实验室开展了试验研究。比较了固体涂层法(SLM)与覆冰水电导率法(IWCM)2种不同染污方式对其冰闪电压的影响,分析了覆冰水电导率、染污盐密、覆冰质量、覆冰密度对110kV支柱绝缘子ZS-126/4覆冰闪络特性的影响。研究结果表明,110kV支柱绝缘子ZS-126/4最低闪络电压与覆冰水电导率、染污盐密、覆冰质量、覆冰密度满足负幂指数函数关系,得到的拟合公式计算结果与试验结果的误差<10%。研究结果可为我国重覆冰地区变电站支柱绝缘配置和设计提供参考。 By measuring AC flashover characteristics of 110 kV ice-covered post insulator ZS-126/4 in the multifunctional artificial climate chamber of Chongqing University, we studied the icing flashover characteristics of the post insulator, compared the effects of two polluting methods, namely solid-layer method (SLM} and icing-water conductivity method (IWCM)), on icing flashover voltage of the post insulator, and analyzed the influences of icing- water conductivity, salt deposit densities, ice weight and ice density on icing flashover performance of specimen. Experimental results show that the relationships between the minimum flashover voltage and icing-water conductivity, salt deposit densities, ice weight, ice density can he expressed as negative exponential functions. The difference between the calculated results from the fitting functions and the tested results is less than 10%. The results offer some consultation for external insulation selection and designing of transmission lines in seriously icing regions.
出处 《高电压技术》 EI CAS CSCD 北大核心 2012年第9期2397-2402,共6页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724501 2009CB724502) 国家创新研究群体基金(51021005)~~
关键词 110kV 支柱绝缘子 覆冰 交流(AC) 闪络特性 染污方式 110 kV post insulator icing alternating current{AC) flashover performance polluting methods
  • 相关文献

参考文献21

二级参考文献138

共引文献393

同被引文献42

  • 1蒋兴良,苑吉河,孙才新,张志劲,胡建林.绝缘子覆冰及其电气试验方法探讨[J].高电压技术,2005,31(5):4-6. 被引量:38
  • 2郭炳信.电网污闪和雪闪故障原因分析及预防措施[J].内蒙古电力技术,2006,24(4):10-12. 被引量:5
  • 3DL/T 859-2004.高压交流系统用复合绝缘子人工污秽试验[S].2004.
  • 4王岩,舒立春,苑吉河,蒋兴良.覆冰绝缘子串的交流闪络特性和放电过程[J].高电压技术,2007,33(9):24-27. 被引量:16
  • 5Meghnefi F, Farzaneh M, Volat C. Measurement of the evolution of dripping water conductivity of an ice-covered insulator during a melt- ing period[C]//Conference on Electrical Insulation and Dielectric Phenomena. Quebec, Canada: [s.n.], 2008: 236-239.
  • 6Farzaneh M, Fofana I, Hemmatjou H. Effects of temperature and impurities on the DC conductivity of snow[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(1): 185-193.
  • 7Farzaneh M, Fofana I, Tavakoli C, et al. Dynamic modelling of DC arc discharge on ice surfaces[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2003, 10(3): 463-474.
  • 8Zhang J, Farzaneh M. Propagation of AC and DC arcs on ice surfac- es[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2000, 7(2): 269-276.
  • 9Liu Y P, Gao S, Huang D C, et al. Icing flashover characteristics and discharge process of 500 kV AC transmission line suspension insulator strings[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2010, 17(2):434-442.
  • 10Farzaneh M, Baker T, Brown K, et al. Insulator icing test methods and procedure[J]. IEEE Transactions on Power Delivery, 2003, 18(4): 1503-1515.

引证文献4

二级引证文献23

相关作者