期刊文献+

计及逆变型分布式电源控制特性的配电网故障分析方法 被引量:58

Fault Characteristics Analysis of Distribution Networks Considering Control Scheme of Inverter Interfaced Distributed Generation
下载PDF
导出
摘要 随着分布式电源(DG)的大量接入,DG的故障穿越行为对配电网的故障特性影响很大。而传统的等值模型均未计及DG的控制策略,从而造成含DG的配电网故障分析存在不可忽略的局限性。为此,文中在系统分析DG控制策略和动作行为的基础上,建立了计及控制策略的逆变器并网方式下DG压控电流源等值模型,更加真实地体现出DG故障电流的输出特性。在此基础上,通过建立故障前后电网支路电流和节点电压关系方程,推导出故障穿越时DG输出电流与公共连接点电压的求解方程组,从而建立故障精确分析方法。最后,基于DIgSILENT建立含DG的10kV配电网仿真模型,验证了所述方法的正确性和有效性。 With the integration of large quantities of distributed generators (DGs) to the grid, the ride-through behavior of DGs has significant impact on the fault characteristics of a distribution network. However, control strategy was not considered in the traditional equivalent model and this caused significant limitations on fault analysis of distribution network with DG.s. By analyzing the control scheme and behavior of DGs, this paper presents a voltage-control current source equivalent model for DGs with an inverter interface taking its control scheme into account. This model reflects the output characteristics of DGs even better. Based on this, the equations between the node voltage and feeder current before and after fault are derived. Then, the equations describing the relationship between fault current of DG and point of common coupling (PCC) are built; and the precise method for fault analysis is thus obtained. A 10 kV distribution network ease is built in DIgSILENT to validate the proposed method.
出处 《电力系统自动化》 EI CSCD 北大核心 2012年第18期92-96,108,共6页 Automation of Electric Power Systems
基金 国家重点基础研究发展计划(973计划)资助项目(2009CB219704) 粤港关键领域重点突破项目(2009A091300011) 广东省教育部产学研结合重点/重大项目(2011A090200127 2011A090200074)~~
关键词 分布式电源 控制策略 故障穿越 等值模型 故障分析 配电网 distributed generator control scheme ride-through equivalent model fault analysis distribution network
  • 相关文献

参考文献14

  • 1IEEE Std 1547.2-2008 IEEE application guide for IEEE Std 1547, IEEE standard for interconnecting distributed resources with electric power systems[S]. 2008.
  • 2BAGHAEE H R, MIRSALIM M, SANJARI M J, et al. Effect of type and interconnection of DG units in the fault current level of distribution networks [C ]// Proceedings of the 13th International Power Electronics and Motion Control Conference, September 1-3, 2008, Poznan, Poland: 313-319.
  • 3NIMPITIWAN N, HEYDT G T, AYYANAR R, et al. Fault current contribution from synchronous machine and inverter based distributed generators [J]. IEEE Trans on Power Delivery, 2007, 22(1): 634-641.
  • 4BARKER P P, DE MELLO R W. Determining the impact of distributed generation on power systems: Part 1 radial distribution systems [C]// Proceedings of the IEEE Power Engineering Society Transmission and Distribution Conference,Vol 3, July 16-20, 2000, Seattle, WA, USA: 1645-1656.
  • 5BARAN M E, EL-MARKABY I. Fault analysis on distribution feeders with distributed generators[J]. IEEE Trans on Power Systems, 2005, 20(4): 1757-1764.
  • 6MARTINEZ J A, MARTIN-ARNEDO J. Impact of distributed generation on distribution protection and power quality [C]// Proceedings of the 2009 IEEE Power and Energy Society General Meeting, July 26-30, 2009, Calgary, Canada: 6p.
  • 7MCDERMOTT T E, DUGAN R C. Distributed generation impact on voltage sags in distribution networks [ C]// Proceedings of the 2002 Rural Electronic Power Conference, May 5-7, 2002, Colorado Springs, CO, USA: 7p.
  • 8GIRGIS A, BRAHMA S. Effect of distributed generation on protective device coordination in distribution system [C]// Proceedings of the Large Engineering Systems Conference on Power Engineering, July 11-13, 2001, Halifax, Canada: 115-119.
  • 9WAN Hui. Protection coordination in power system with distributed generation [D]. Hong Kong, China: The Hong Kong Polytechnic University, 2006.
  • 10孙景钌,李永丽,李盛伟,金强.含逆变型分布式电源配电网自适应电流速断保护[J].电力系统自动化,2009,33(14):71-76. 被引量:74