摘要
500kV主变低压套管接线端子是由于本身设计不合理,接线板与抱箍台阶呈90°的直线连接,应力非常集中,合金内部有杂质及浇铸工艺不合理,导致边缘产生结晶带的组织,就断裂原因进行分析及提出了改进措施。
The connecting terminal fractured due to its irrational design. The terminal board and holt hoop iron step were combined in 90°, which led to the highly intensively stress. There was also impurity in the alloy. The irrational casting technology led to the generation of crystalline band in the edge.
出处
《贵州电力技术》
2012年第9期1-5,共5页
Guizhou Electric Power Technology
关键词
变压器
低压套管接线端子
断裂
原因分析
改进措施
transformer
low- voltage bushing connecting terminal
fracture
reason analysis
improvement measures