期刊文献+

线路光差保护改载波保护运行探讨与实践

Discussion and practice on line carrier protection replacing optical differential protection
下载PDF
导出
摘要 阐述了在500kV大黔双回线、黔烽Ⅰ回线停电加固期间500kV黔烽Ⅱ回线路光差保护没有光纤通道,临时将黔烽Ⅱ回线路光差保护改造成载波保护运行,成功解决了在500kV大黔双回线、黔烽Ⅰ回线停电加固期间,黔烽Ⅱ回线路只单主保护运行。 This paper expounded the 500 kV Qianfeng Ⅱ back line had not fiber channel for optical differential protection during the 500 kV Daqian double line and Qianfeng Ⅰ back line at the time what power failure and reinforcement. Temporarily transformed Qianfeng Ⅱ back line optical differential protection into carrier protection operation, successfully solved the problem of Qianfeng Ⅱ back line only single primary protection operation during the 500 kV Daqian double line and Qianfeng Ⅰ back line power failure and reinforcement.
作者 晋斌
机构地区 贵阳供电局
出处 《贵州电力技术》 2012年第9期81-82,40,共3页 Guizhou Electric Power Technology
关键词 光差保护 载波保护 保护改造 通道改造 optical differential protection carrier protection protection modification channel reconstruction.
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部