石家庄公共场所集中空调通风系统微生物污染监测与评价 被引量:3

Monitoring and evaluation on microbial pollution of centralized air ventilation system in public places in Shijiazhuang
原文传递
导出
摘要 目的分析石家庄市集中空调通风系统卫生状况,为加强集中空调通风系统的消毒管理提供技术支持。方法按照《公共场所集中空调通风系统卫生规范》,对公共场所集中空调通风系统的冷凝水、冷却水、积尘、空气分别进行采样、检测。结果通风管积尘:总合格率57.6%;送风口空气:总合格率74.8%;冷却水、冷凝水中嗜肺军团菌:总合格率79.5%。结论石家庄市的空调通风系统存在着一定的卫生问题,建议定期清洗消毒,加强监管。 Objective To analyze the sanitary conditions of central air ventilation system m 3nljlaznuang, ano provide technical support for strengthening the disinfection management of centralized air ventilation system. Method Sample and detect the condensate water, cooling water, dust, air in central air ventilation systems, respectively in accordance with Sanitary Specification of Central Air Ventilation Systems in Public Places. Re sults The overall qualified rate of dust in ventilating duct was 57.6% ; the qualified rate of air in air distribu tor was 74. 8% ; and the qualified rate of legionella pneumophila in cooling and condensate water was 79.5%. Conclusion There were some sanitation problems in air ventilation system in Shijiazhuang, thus we suggested to clean and disinfect them regularly, and strengthen supervision.
作者 张立华
出处 《医学动物防制》 2012年第10期1086-1087,1090,共3页 Journal of Medical Pest Control
关键词 集中空调 消毒 监管 Central air conditioning Sterilization Monitoring
  • 相关文献

参考文献3

  • 1北京市人民政府.北京市集中空调通风系统卫生管理办法.2011-04-01.
  • 2卫生部.卫生部令第80号公共场所卫生管理条例实施细则.2011-03-10.
  • 3中华人民共和国商务部.SB/T10594-2011集中空调通风系统清洗行业技术管理规范[s].北京:中国标准出版社,2011.

同被引文献114

  • 1于凌琪,王书梅,张致一,王菲,薛志明,刘洪亮.天津市四星级以上宾馆集中空调通风系统微生物污染调查[J].环境与健康杂志,2008,25(1):65-66. 被引量:1
  • 2冯文如.军团菌在空调系统中的传播和控制[J].中国人兽共患病学报,2006,22(1):78-80. 被引量:11
  • 3刘玲,刘一君,郭小玲,沈峻.湖北省公共场所卫生状况调查[J].公共卫生与预防医学,2007,18(1):90-91. 被引量:4
  • 4李泉,付洁,马弋,杨晓敏,谢茂慧.湖北省三市集中式中央空调冷却塔水军团菌污染状况调查[J].公共卫生与预防医学,2007,18(2):50-51. 被引量:5
  • 5WHO. Legionella and the prevention of Legionellonsis [ M ] . India, 2007 : 70.
  • 6Sala-Ferr6 MR. Monitoring of biofilm-associated Legionella pneumophila on different substrata in model cooling tower system[J]. Eur J Clin Microbiol Infect Dis, 2009, 28:153-159.
  • 7Freudenmann M, Kurz S, yon Baum H. Interdisciplinary management of a large Legionella outbreak in Germany [ J ]. Bundesgesundheitsbl, 2011,54:1161-1169.
  • 8曹春远,陈前进,张景平,等.龙岩市2006.2010年部分公共场所水体军团菌污染状况调查分析[c]//第二届传染病防控基础研究与应用技术论坛论文集.2011:181-187.
  • 9高建民,李柱锋,老倩群,等.顺德区公共场所集中空调通风系统微生物污染状况调查与分析[J].中外健康文摘,2013,10(19):8-9.
  • 10Robert LS, Benjamin LW, Leslie E L. The influence of rapid onsite evaluation on the adequacy rate of fine-needle aspiration cytology: a systematic review and mela-analysis[J ]. Am J Cli Pathol,2013, 139: 300-8.

引证文献3

二级引证文献16

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部