期刊文献+

10kV开关柜局部放电检测技术研究与运用 被引量:61

Research on the Partial Discharge Detection Technology for 10 kV Switchgear
下载PDF
导出
摘要 10 kV开关柜作为中国配网系统中非常重要的设备,其运行的可靠性直接关系到供电可靠性。开关柜内的绝缘缺陷或劣化、接触不良等都会成为其安全运行的隐患,而这些隐患在设备正常运行的情况下又很难发现。为解决上述问题,笔者介绍了基于暂态对地电压(TEV)、超声波(AE)、超高频(UHF)原理的联合局部放电检测方法。该方法可以为评估开关柜运行状态和检修工作提供丰富的数据依据,全面保障10 kV开关柜的安全运行。 10 kV switchgears are important equipment in Chinese power distribution networks. The defects such as insulation degradation and poor contacts in a 10 kV switchgear,which are difficult to be detected while the switchgear is operating normally,may harm its safe operation. Therefore,this paper proposes a joint partial discharge detection method based on the principles of transient earth voltage (TEV),ultrasonic (AE),and ultra high frequency (UHF). switchgear to guarantee safe The method can offer sufficient data for status evaluation and maintenance of the operation.
机构地区 佛山供电局
出处 《高压电器》 CAS CSCD 北大核心 2012年第10期100-104,共5页 High Voltage Apparatus
关键词 开关柜 局部放电 暂态对地电压 超声波 超高频 switchgear partial discharge transient earth voltage (TEV) ultrasonic (AE) ultra high frequency(UHF)