期刊文献+

分液冷凝器在HFC410A空调系统的替换实验研究 被引量:2

Experimental Investigation of HFC410A Air-conditioning System Substituted for Liquid-vapor Separation Condenser
下载PDF
导出
摘要 汽液分离式冷凝器是一种管内高效冷凝换热器,它采用了一些强化换热手段,如多管程平行流冷凝、中间排液以及优化管子数目等。这里将该分液冷凝器用于HFC410A空调系统中,并进行了性能测试。结果表明:使用分液冷凝器后,HFC410A的制冷能力仅为原系统的96.4%,EER值为原来的93.8%,该分液冷凝器无法实现替换目的。通过分析发现,HFC410A对分液冷凝器的热力性能影响较大,HFC410A在分液冷凝器的气液分离效果变差,不再维持HCFC22在分液冷凝器中表现出来的近等温冷凝过程;在相同的冷凝温度下,HFC410A系统的循环质量流量较HCFC22系统减少1.2%~9.2%时,分液冷凝器的压降提高39.1%~52.6%。 Liquid-vapor separation condenser(LSC) is a kind of heat exchanger with high in-tube condensation heat transfer coefficient.It adopts some enhancement means,such as the parallel flow condensation with multi tube passes,draining away condensate between two adjacent passes and optimization of the tube number of refrigerant route.In the present paper,the LSC was applied in an HFC410A air conditioning system and measured in the standard air enthalpy difference lab.Compared with the prototype HFC410A system,the cooling capacity and EER of the LSC system were 96.4% and 93.8% respectively.The results present the LSC is a poor substitution for the original condenser.The analysis shows HFC410A reduced the performance of LSC by weakening the liquid-vapor separation effect,which results in the condensation process in HFC410A LSC no longer keeping the quasi-constant wall temperature as that in the HCFC22 LSC.The looping refrigerant mass flux in the HFC410A system was 1.2%~9.2% lower than that of HCFC22 system at the same condensation temperature,and the pressure drop of the LSC in HFC410A system was seen to increase by 39.1%~52.6%.
出处 《制冷学报》 CAS CSCD 北大核心 2012年第5期26-31,共6页 Journal of Refrigeration
基金 国家自然科学基金(50976054)资助项目~~
关键词 热工学 制冷性能 焓差法 分液冷凝 Pyrology Refrigerating performance Enthalpy difference method Liquid-vapor separation condensation
  • 相关文献

参考文献10

  • 1马一太,王伟.制冷剂的替代与延续技术[J].制冷学报,2010,31(5):11-17. 被引量:68
  • 2Cavallini A, Censi G, Del Col D, et al. Experimental investigation on condensation heat transfer and pressure drop of new HFC refrigerants (R134a, R125, R32, R410A, R236ea) in a horizontal smooth tube[J]. International Journal of Refrigeration, 2001, 24 (1) : 73-87.
  • 3黄理浩,陶乐仁,郑志皋,王伟,张建国,张庆钢,王金锋.R410A应用于内螺纹强化管的蒸发实验研究[J].制冷学报,2010,31(6):12-15. 被引量:9
  • 4刘荣,陶乐仁,高立博,薛维超,张玲玲,成简,张庆刚.R410A在内螺纹管内无润滑油沸腾换热实验研究[J].制冷学报,2011,32(4):20-24. 被引量:18
  • 5Kim M H, Bullard C W. Dynamic characteristics of a R-410A split air-conditioning system[J]. International Journal of Refrigeration, 2001, 24 (7) : 652-659.
  • 6Chert W. A comparative study on the performance and environmental characteristics of R410A and HCFC22 residential air conditioners[J]. Applied thermal engineering, 2008.28(1): 1-7.
  • 7彭晓峰,吴迪,张扬.高性能冷凝器技术原理与实践[J].化工进展,2007,26(1):97-104. 被引量:42
  • 8McLinden M O, Klein S A, Lemmon E W, et al. Thermodynamic and transport properties of refrig- erants and refrigerant mixtures[CP/DK]. NIST Standard Reference Database-version 6.01, 1998.
  • 9Chen Y, Hua N, Deng L S. Performances of a split- type air conditioner employing a condenser with liquid- vapor separation baffles[J]. International Journal of Refrigeration, 2012, 35 (2): 278-289.
  • 10Holman J P, Gajda W J. Experimental Methods for Engineers[M]. McGraw-Hill Inc., New York, 1989: 41-42.

二级参考文献38

共引文献129

同被引文献13

引证文献2

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部