摘要
目的通过对昆山市23家星级宾馆客房空气质量的调查分析,了解该市星级宾馆客房的空气质量现状。方法于2010年4月—2011年3月,随机选取昆山市使用集中空调通风系统的3~5星级宾馆23家。依据GB/17220-1998《公共场所卫生监测技术规范》的要求在其客房内,设立监测点,共设立监测点409个,对客房内温度、湿度、细粒子等11项指标进行连续监测。结果共监测到数据4 323个,一氧化碳、风速、甲醛3项指标的合格率较高,分别为100.0%、97.7%、91.0%;噪声、湿度、菌落总数的合格率较低,分别为39.1%、46.4%、53.6%。结论昆山市星级宾馆客房的空气质量总体良好,但客房的噪声、湿度合格率较低,应该采取相应的措施加以改善。
[Objective]To explore the indoor air quality of bedrooms in star hotels by investigating 23 star hotels in Kunshan City.[Methods]According to "Monitoring Technical Specifications for Hygiene in Public Places" GB/17220-1998,temperature,humidity,PM2.5 and other 8 indicators were continuously monitored in 409 monitoring stations which were set up in bedrooms of 23 3-5 star hotels in which central air conditioning was used as ventilation system in Kunshan City from April 2010 to March 2011.[Results] There were 4 323 records of environment surveillance data,the qualified rates of carbon monoxide,wind velocity,and formaldehyde were relatively high(100.0%,97.7%,91.0%,respectively).The qualified rates of noise,humidity and aerobic bacterial were separately 39.1%,46.4%,53.6% which were relatively low.[Conclusion]The air quality of star hotel bedrooms is good in general in Kunshan city,but the qualified rates of noise,humidity are low which needs to take appropriate measures for improvement.
出处
《职业与健康》
CAS
2012年第19期2401-2402,共2页
Occupation and Health