摘要 针对卷烟厂室内温湿度控制精度较高、湿负荷小、热湿比大的特点及传统空调系统采用恒定7℃冷水温度而导致的一些问题,利用DeST模拟分析了位于全国不同气候分区的5个城市的卷接包和制丝车间分别在23℃和25℃两个室内设定温度下全年对冷水温度的实际要求,通过实验研究验证了提高冷水供水温度的可行性,分析了提高冷水供水温度的节能性。结果表明,冷水需求温度为8~15℃;当夏季供10℃、过渡季和冬季供12℃的冷水时,夏季可实现冷水机组节能13%,过渡季和冬季可实现节能23%。 Cigarette factories have the characteristics of high requirement for temperature and humidity control, lower humidity load and larger heat humidity ratio. The chilled water supply temperature of conventional air conditioning system is kept constant at 7 ℃ in cigarette factories and leads to some problems. By the DeST software, simulates and analyses the annual required chilled water temperature in the cigarette-packing workshop and the primary processing workshop in five cities located at five different climatic zones at the different setting indoor temperature of 23 ℃ and 25 ℃. Experimentally verifies ;he feasibility of improving the chilled water supply temperature and analyses the energy efficiency. The results indicate that the required chilled water temperature is 8 ℃ to 15 ℃ ; when the supply temperature is 10 ℃ in summer and 12 ℃ in transition seasons and winter, the energy saving rate can be 13% in summer and 23% in transition seasons and winter.
机构地区 清华大学 东华大学
出处 《暖通空调》 北大核心 2012年第11期143-148,共6页 Heating Ventilating & Air Conditioning
关键词 卷烟厂 空调系统 提高冷水温度 冷水需求温度 节能 cigarette factory, air conditioning system, improving chilled water temperature, required chilled water temperature, energy efficiency
  • 相关文献

参考文献8

二级参考文献55

  • 1彭京砥,娄开立.现有烟草空调器存在的问题及其改进方法[J].暖通空调,1992,21(1):42-45. 被引量:1
  • 2李永安,常静,徐广利,戎卫国,刘学来.封闭式冷却塔供冷系统气象条件分析[J].暖通空调,2005,35(6):107-108. 被引量:22
  • 3杜荣杰,邢优诚,尤长虹,李兵役,方敏,牛燕丽.卷烟卷制质量与车间温湿度的关系[J].烟草科技,2007,40(1):10-12. 被引量:16
  • 4敖顺荣.卷烟厂空调系统全年动态多工况恒温恒湿节能控制策略的研究[C]//2008节能环保建筑新技术新产品应用论文汇编.北京:中国住房和城乡建设部科学技术委员会,2008.
  • 5T L White.A winter cooling tower operation for a central chilled water system[R].ASHRAE Transactions.1994,100,Part l:800-816.
  • 6张睛原,Joe Huang.中国建筑用标准气象数据库[M].北京:机械工业出版社,2004.
  • 7[1]Mr. Rob Moult. Building automation for a green building[R] Green Building Congress 2001.
  • 8Malcolm Orme. Applicable models for air infiltration and ventilation calculations. AIVC Technical Note 51
  • 9Jiang Y. State space method for analysis of the thermal behavior of room and calculation of air conditioning load. In:ASHRAE Trans. 1981, 88(2): 122- 132
  • 10H Tianzhenong, Jiang Yi. A new multizone model for the simulation of building thermal performance. Building and Environment, 1997, 32:123~128