期刊文献+

220kV变压器绝缘深度受潮的现场干燥处理方法 被引量:3

On-Site Dry Disposal of Serious Wetting for 220 kV Transformer Insulation
下载PDF
导出
摘要 对于深度受潮的变压器,利用热油喷淋干燥,可有效提高绝缘水平,介绍了热油喷淋干燥的原理,阐述了喷淋干燥系统、真空系统、绝缘电阻测量回路,并结合喷淋干燥过程和喷淋干燥实例数据,对干燥结果进行了判断,通过热油喷淋干燥前后变压器的绝缘效果的对比,结果证明该喷淋干燥系统的良好效果。 For the transformer of serious wetting, deep fat spray dry could raise insulation level effectively. Introduction was made to the principle of deep fat spray dry. This paper expatiated on the spray dry system, the vacuum system and the measurement circuit of insulation resistance, combining with the process and the data of example of spray dry to judge the dry result. By contrast to the insulation effect of deep fat spray dry before and after, the result verified the good effect of this spray dry system.
出处 《电工电气》 2012年第11期52-55,共4页 Electrotechnics Electric
关键词 变压器 绝缘 绝缘电阻 喷淋干燥 transformer insulation insulation resistance spray dry
  • 相关文献

参考文献2

  • 1变压器制造技术丛书编审委员会.变压器处理工艺[M].北京:机械工业出版社,2000.
  • 2钟洪壁,高占邦,王正官,王世阁.电力变压器检修与试验手册[K].北京:中国电力出版社,2000.

同被引文献25

  • 1陈训耀.降低高压变压器现场安装时油中含气量的方法[J].高压电器,2005,41(5):397-398. 被引量:8
  • 2董宝骅.变压器在正常工作电压下的绝缘事故原因分析及防御措施[J].电力设备,2005,6(11):63-66. 被引量:7
  • 3GB 50150--2006电气装置安装工程电气设备交接试验标准[S].
  • 4DL/T580-1995用露点法测定变压器绝缘纸中平均含水量的方法[S].
  • 5DL/T596-2005,电力设备预防性试验规程[S].
  • 6GB 50150-2006 电气装置安装工程电气设备交接试验标准[S],2006.
  • 7GB50148-2010,电气装置安装工程电力变压器、油浸电抗器、互感器施工及验收规范[S].
  • 8电气装置安装工程电力变压器、油浸电抗器、互感器施工及验收规范GB50148-2010[S].国家电网公司,2010.
  • 9何伟然.变压器的充氮保管[J].华东电力,1987(5):48-50.
  • 10OommenT、‘赵宗平.用于变压器绝缘干燥工艺的含水量平衡曲线图[J].变压器,1985(4):26-29.