单母线分段接线中备用电源自动投入装置的改进 被引量:15

Improvement of Automatic Transfer Switch for Backup Power Supply Used in Sectionalized Single-bus Configuration
下载PDF
导出
摘要 为保证对用户可靠供电,110kV变电站常配有备用电源自动投入装置。在备用电源自动投入装置动作过程中,若断路器拒跳,将造成变电站全站停电。分析了一起110kV变电站全站停电事故,指出常规进线备用电源自动投入装置动作逻辑的不足,提出了进线备用电源自动投入装置的改进方案。 The 110 kV substation often equips with automatic transfer switch (ATS) for backup power supply in order to ensure the reliability of power supply. If the circuit breaker rejects operation when ATS operates, it may cause the power supply failure of the whole station. The power supply failure of 110 kV substation has been analyzed. Operation logic shortcomings of normal ATS are pointed out, and an improved scheme of incoming line ATS is proposed.
出处 《电力系统自动化》 EI CSCD 北大核心 2012年第22期120-122,共3页 Automation of Electric Power Systems
关键词 单母线分段接线 备用电源 自动投入装置 开关拒动 供电可靠性 全站停电 sectionalized single-bus configuration backup power supply automatic transfer switch switch operation rejection power supply reliability power supply failure of whole station