期刊文献+

110kV备自投存在的运维问题及应对措施

The operation and maintenance problem of 1 lOkV backup self- switching equipment and its countermeasures
下载PDF
导出
摘要 以110kV某站为例,对其110kV备自投装置存在的某些运行方式下备自投无法充电、备自投动作后合闸于故障母线时故障无法快速切除、开关位置取自操作箱TWJ(跳闸位置继电器)而引起备自投放电动作失败三方面的运维问题进行分析,并提出相应的应对措施。 Took a 110 kV substation for example, there were three operation and maintenance problems for 110 kV backup self - switching equipment, that backup self - switching equipment problem could not be charged under certain operating mode, failure could not be removed rapidly when backup self - switching equipment problem switch into the fault bus, backup self - switching equipment problem fails due to switch position fed from the relay at trip position in the operation box. The solutions were put forward accordingly, and useful reference was given to the design of 110 kV backup self- switching equipment problem and operation and maintenance.
作者 吕然
出处 《贵州电力技术》 2012年第11期42-44,共3页 Guizhou Electric Power Technology
关键词 110 kV备自投 运行方式 措施 110 kV backup self- switching equipment problem operation mode measure
  • 相关文献

参考文献5

  • 1国家电力调度通讯中心.国家电网公司继电保护培训教材(下册)[M].北京:中国电力出版社,2009.
  • 2广东电网110kV侧备自投装置标准化设计要求[z].2011.
  • 3DPR320AT系列数字式备用电源自投装置[z].2011.
  • 4NDB310系列数字式备用电源自投装置[Z].2007.
  • 5NSA-3152WGl四进线备用电源自投装置[z].2012.