摘要 四川省德阳地区110kV电网是以一个220kV变电站为电源中心呈辐射状向各负荷变电站供电的运行方式,通过对220kV变电站110kV出线采用双回线并列运行且分别运行在两段母线上,当110kV单回线路发生故障时线路开关或线路保护拒动的分析,得出了220kV变电站110kV母线将发生电网大面积停电事故的结论,提出了采用改变电网运行方式消除外挂母联和调整保护方案(采用事故发生后以一较短时限先跳开220kV变电站110kV母联开关,再跳双回线路负荷侧开关的保护时限配合原则,保证故障母线与非故障母线隔离)两种解决措施,均可避免发生220kV变电站110kV母线全停的电网大面积停电事故。 110 kV power grid of Deyang area in Sichuan Province is a power supply center of 220 kV transformer substations,whose operation mode is radial power supply to the load transformer substation.This paper deeply analyzes the power grid structure and operation mode when 110 kV single loop line of 220 kV substation aborts.If the fault lines take place line switch or protection refuse operating,it will lead to 110 kV bus of 220 kV substation full cut-off and trigger large area blackout accident.So,it puts forward treatment measures including change the power grid operation mode to remove the cladding bar coupler or adjustment protection plan(when the accident happened,in a short time tripping off 110 kV bar coupler of 220 kV substations,then tripping off switch of double loop line load to ensure the fault bus bar isolation).These two measures can avoid 110 kV bus of 220 kV substations full cut-off and large area blackout accident.
出处 《水电能源科学》 北大核心 2012年第11期162-166,共5页 Water Resources and Power
关键词 220KV变电站 110kV开关 拒动 分析 措施 220 kV substation 110 kV switch refuse operation analysis measure
  • 相关文献

参考文献4

  • 1四川省电力公司,重庆市电力公司,北京市电力公司,等.3kV-110kV电网继电保护装置运行整定规程(DL/T584-2007)[S].北京:中国电力出版社,2008.
  • 2华东电力调度通信中心,国家电力调度通信中心,浙江电力调度通信中心,等.220kV-750kV电网继电保护装置运行整定规程(DL/T559-2007)[S].北京:中国电力出版社,2008.
  • 3华东电力设计院,华北电力设计院,四川电力调度中心,等.继电保护及安全自动装置技术规程(GB/T14285-2006)[S].北京:中国标准出版社,2006.
  • 4卓乐友.电力工程电气设计手册(电气二次部分)[M].北京:水利电力出版社,1990-09.

共引文献1

同被引文献44

引证文献3

二级引证文献12

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部