摘要
建立了基于EnergyPlus的地板辐射供冷加置换通风空调系统模型,模拟得到的室内温度和辐射地板所承担冷量与实验结果的误差小于±7%。在此模型基础上,改变送风参数和供水参数,得到置换通风供冷量、辐射地板供冷量、地板表面温度、室内空气平均温度、AUST温度等参数的变化规律。结合热舒适性模型,得到满足室内热舒适性(-0.5≤PMV≤0.5)条件下,置换通风的送风参数和辐射地板的供水参数范围,为复合系统设计和应用提供依据。
The simulation model of hybrid radiant cooling floor and displacement ventilation air conditioning system was built and analyzed by software EnergyPlus. By comparing the simulation results and experimental data, it is shown that the simulated indoor air temperature and cooling capacity provided by radiant floor was ±7% deviated from the experimental data. Based on the model, with the change of supply air parameters or supply water parameters, the cooling capacity provided by radiant floor and displacement ventilation, surface temperature of radiant floor, indoor air average temperature, AUST temperature were obtained. Combined with the indoor thermal comfort model, when indoor thermal comfort index PMV varied between -0.5 and 0. 5, the recommended supply air and supply water parameters were obtained to provide reference for engineering design and application.
出处
《土木建筑与环境工程》
CSCD
北大核心
2012年第6期115-119,共5页
Journal of Civil,Architectural & Environment Engineering
基金
陕西省自然科学基金(2011JQ7021)
陕西省教育厅科研计划项目(11JK0941)
关键词
空调
辐射供冷
置换通风
模拟
热舒适
air conditioning
radiant cooling
displacement ventilation
systems analysis
thermal comfort