地板辐射与置换通风空调系统运行参数 被引量:8

Operational Parameters of Hybrid Radiant Cooling Floor and Displacement Ventilation Air Conditioning System
下载PDF
导出
摘要 建立了基于EnergyPlus的地板辐射供冷加置换通风空调系统模型,模拟得到的室内温度和辐射地板所承担冷量与实验结果的误差小于±7%。在此模型基础上,改变送风参数和供水参数,得到置换通风供冷量、辐射地板供冷量、地板表面温度、室内空气平均温度、AUST温度等参数的变化规律。结合热舒适性模型,得到满足室内热舒适性(-0.5≤PMV≤0.5)条件下,置换通风的送风参数和辐射地板的供水参数范围,为复合系统设计和应用提供依据。 The simulation model of hybrid radiant cooling floor and displacement ventilation air conditioning system was built and analyzed by software EnergyPlus. By comparing the simulation results and experimental data, it is shown that the simulated indoor air temperature and cooling capacity provided by radiant floor was ±7% deviated from the experimental data. Based on the model, with the change of supply air parameters or supply water parameters, the cooling capacity provided by radiant floor and displacement ventilation, surface temperature of radiant floor, indoor air average temperature, AUST temperature were obtained. Combined with the indoor thermal comfort model, when indoor thermal comfort index PMV varied between -0.5 and 0. 5, the recommended supply air and supply water parameters were obtained to provide reference for engineering design and application.
出处 《土木建筑与环境工程》 CSCD 北大核心 2012年第6期115-119,共5页 Journal of Civil,Architectural & Environment Engineering
基金 陕西省自然科学基金(2011JQ7021) 陕西省教育厅科研计划项目(11JK0941)
关键词 空调 辐射供冷 置换通风 模拟 热舒适 air conditioning radiant cooling displacement ventilation systems analysis thermal comfort
  • 相关文献

参考文献13

  • 1Jeong J W, Mumma S A, Bahnfleth W P. Energy conservation benefits of a dedicated outdoor air system with parallel sensible cooling by ceiling radiant panels [J]. ASHRAE Transaction, 2003,109 (2) : 627-636.
  • 2Catalina T, Virgone J, Kuznik F. Evaluation of thermal comfort using combined CFD and experimentation study in a test room equipped with a cooling ceiling [J]. Building and Environment, 2009,44 : 1740-1750.
  • 3Vangtook P, Chirarattananon S. An experimental investigation of application of radiant cooling in hot humid climate[J]. Energy and Building, 2006,38 : 273- 285.
  • 4Lim J H, Jo J H, Kim Y K, et al. Application of the control methods for radiant floor cooling system in residential buildings [J]. Building and Environment, 2006,41:60-73.
  • 5Mumma S A, Jeong J W. Direct digital temperature, humidity, and condensate control for a dedicated outdoor air-ceiling radiant cooling panel system [J]. ASHRAE Transaction,2005,111(part 1) :547-558.
  • 6Xuan Y M, Huang X, Kang N, et al. Experimental study of a hybrid radiant cooling air conditioning system based on evaporative cooling used in Xi'an city, China [C]//The 7th International Symposium on Heating,Ventilation and Air Conditioning. Shanghai: Tongji University: 27-32.
  • 7黄翔,闫振华,宣永梅.蒸发冷却与毛细管辐射供冷复合空调系统实验研究[J].暖通空调,2009,39(9):34-41. 被引量:11
  • 8闰振华.基于蒸发冷却辐射供冷/热空调系统实验研究[D].西安:西安工程大学,2008.
  • 9宣永梅,黄翔,闫振华,张新利.西北地区使用干空气能的蒸发冷却辐射供冷系统应用分析[J].流体机械,2009,37(2):82-85. 被引量:17
  • 10Novoselac A, Srebric J. A critical review on the performance and design of combined cooled ceiling and displacement ventilation systems [J]. Energy and Buildings, 2002, 34: 497-509.