期刊文献+

110kV庄北变电站保护定值整定中存在的问题及解决方案 被引量:3

Problems Existing in Fixed Value Setting of 110 kV Zhuangbei Substation and Its Solution
下载PDF
导出
摘要 因庄北变电站的负荷属于钢铁冶炼性质,在正常生产时经常出现很大的工作短路电流,引起保护的频繁启动及误动作,经过对运行方式的调整及保护装置的升级,对变压器保护配置及出口回路的调整,确保了用户供电的可靠性及电网主设备的安全运行。该方案对于相似负荷性质的供电网络有一定的参考作用,针对运行经验提出了继电保护与运行方式的密切联系,同时对电网建设部门的设备选型提出了要求。 Because the load characteristics of Zhuangbei Substation belong to the style of iron and steel melting, the large service short - circuit current ofter occurs during the normal operation, which will cause the frequent action and miss operation of the protection. Through changing the operating mode and updating the protection device, the regulation for the protection con- figuration and outlet circuit of transformer will guarantee the reliability of power supply and the stable operation of gird main equipment. The proposed scheme provides some references for power supply system with the same load characteristics, the close relationship between relay protection and operating mode is presented incorporating the operation experiences, and the requirements for the equipment type selection of grid construction departments are proposed too.
出处 《四川电力技术》 2012年第6期36-39,共4页 Sichuan Electric Power Technology
关键词 继电保护 定值 整定计算 relay protection fixed value setting calculation
  • 相关文献

参考文献4

二级参考文献15

  • 1贺以燕.关于电力变压器承受短路能力问题的再探讨[J].变压器,1996,33(11):2-4. 被引量:33
  • 2董爱玲,凌玉华,廖力清.变电站主变成套保护装置系统设计[J].国外电子元器件,2006(11):37-42. 被引量:2
  • 3武玉珠.变压器运行中的安全与继电保护[J].内蒙古石油化工,2007,33(6):55-56. 被引量:2
  • 4Q/GDW175-2008.变压器、高压并联电抗器和母线保护及辅助装置标准化设计规范[S].
  • 5DL/T684-1999.大型发电机变压器保护整定计算导则[S].
  • 6GB/T14285-2006,继电保护和自动装置技术规程[S].北京:中国标准出版社,2006.
  • 7GB/T584-2007.3kV-110kV电网继电保护装置运行整定规程[S].北京:中国电力出版社,2008.
  • 8GB1094.5-1985,电力变压器[S].
  • 9GB1094.5-2008.电力变压器第5部分:承受短路的能力[S].北京:中国标准出版社,2008.
  • 10崔家佩,孟庆炎,陈永芳,等.电力系统继电保护与安全自动装置整定计算[M].北京:中国电力出版社,2007.