期刊文献+

数据中心制冷方案比较分析 被引量:3

Analysis and Comparison of Cooling Solutions for IDC
下载PDF
导出
摘要 以北京地区某数据中心机房为例,采用专业软件,建立了风冷式制冷模式、常规水冷式制冷模式、风冷式+经济器制冷模式和水冷式+经济器制冷模式四种不同制冷方案,并对不同方案进行模拟计算,从初投资、电耗量和运行费用方面进行综合分析。研究结果表明无论水冷还是风冷制冷模式,增加经济器后运行费用都会降低。经综合分析,水冷式+经济器制冷模式具有长远优势。 Taking an IDC in Beijing as an example, using professional software, this article sets up air-cooled cooling mode , water-cooled cooling mode, air-cooled+economizer cooling mode, water-cooled+economizer cooling mode and simulates different solutions, from the initial investment, electricity consumption and operation cost and makes a comprehensive analysis of. Results show that after economizer was added, operating costs of both water-cooled or air-cooled cooling mode was reduced, comprehensive analysis shows that water-cooled+economizer cooling mode has a long-term advantage.
出处 《发电与空调》 2012年第5期83-87,共5页
关键词 数据中心 风冷式制冷模式 常规水冷式制冷模式 风冷式+经济器制冷模式 水冷式+经济器制冷模式 IDC air-cooled cooling mode water-cooled cooling mode air-cooled+economizer cooling mode water-cooled+economizer cooling mode
  • 相关文献

参考文献4

二级参考文献7

共引文献11

同被引文献7

引证文献3

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部