天津市公共场所集中空调通风系统卫生状况及影响因素 被引量:20

Hygienic situation and influencing factors for centralized air conditioning ventilation systems in Tianjin
原文传递
导出
摘要 目的了解2011年天津市公共场所集中空调通风系统卫生状况,并探讨其可能的影响因素。方法采用分层随机抽样方法在天津市17个区县抽取128家公共场所,对集中空调通风系统的新风机组类型、新风口位置、清洗状况、公共场所类型及采样点位置等基本情况进行调查。并对风管内表面积尘量、风管内表面细菌总数、风管内表面真菌总数和冷却水嗜肺军团菌进行检测。结果集中空调通风系统风管内表面积尘量合格率为28.1%(36/128),风管内表面细菌总数合格率为95.3%(122/128),风管内表面真菌总数合格率为94.5%(121/128),冷却水中嗜肺军团菌合格率为64.3%(74/115),其中Lp1型嗜肺军团菌为主要血清型。清洗后风管内表面积尘量合格率高于未清洗(P<0.05),清洗与未清洗的全新风式机组风管内表面积尘量合格率高于回风式机组(P<0.05),未清洗的且新风口在室外的机组风管内表面积尘量合格率高于新风口在室内的机组(P<0.05)。结论本次调查的集中空调通风系统风管内表面积尘量合格率较低,并可能受到清洗、空调机组类型和新风口位置等因素影响。 Objective To know the hygienic status and influencing factors of centralized air conditioning ventilation systems in public places in Tianjin, 2011. Methods A total of 128 public places in 17 districts and counties in Tianjin were sampled by stratified randomly sampling and information on central air-conditioning unit types, fresh air position, cleaning condition, public place types and sampling point were investigated, The dust, total bacteria, total fungi on inner surface of air pipe and Legionella pneumophila in cooling water of air conditioning system were tested. Results The qualified rates of dust, total bacteria, total fungi on inner surface of air pipe of centralized air conditioning ventilation systems and Legionella pneumophila in cooling water of air conditioning ventilation system were 28.1%, 95.3%, 94.5% and 64.3%, respectively. The Lpl was the main type of LegioneUa pneumophila. The significant differences in dust on inner surface of air pip were seen in various cleaning condition, various centralized air-conditioning unit types, various fresh air position. Conclusion The qualified rates of dust were lower. The cleaning condition, centralized air-conditioning unit types and fresh air position may have impact on dust on inner surface of air pipe of centralized air conditioning ventilation systems.
出处 《环境与健康杂志》 CAS CSCD 北大核心 2012年第12期1120-1123,共4页 Journal of Environment and Health
关键词 空气污染 室内 公共场所 集中空调 Air pollution, indoor Public places Centralized air conditioning system
  • 相关文献

参考文献11

二级参考文献39

共引文献126

同被引文献150

引证文献20

二级引证文献75

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部